SCROLL 15SP1CB / 13SP2CB – 35SP1CB / 29SP2CB – 52SP1CB / 42SP2CB
12
520606-00
EN
3.6
Cleaning the suction filter or replacement
1)
Remove the suction filter
①
Remove the butterfly nut, then remove the suction filter
2)
Air blow from inside of suction filter
In case that the filter is very and/or damaged, replace to the new one.
3.7
Re-tightening discharge piping
Refer to the following procedure to re-tighten discharge piping after maintenance of air-end in case when removed the
discharge piping tentatively from the air-end during maintenance
Tighten the discharge pipe in the correct procedure as shown below.
1) Finger-tighten the discharge pipe till you cannot
At this stage, do not use the wrench.
2) Put a reference line on the discharge pipe to count turns.
3) Tighten the discharge pipe additional turns shown in table below using wrench.
Over tightening of discharge pipe will cause damage to screw thread of pipe and air-end.
Model
Nominal pipe diameter
Additional turns
15SP1CB / 13SP2CB
3/8B (10A)
4 to 4.5
35SP1CB / 29SP2CB
52SP1CB / 42SP2CB
1/2B (15A)
3 to 3.5