③
Screen
④
Screen clamping rail or cable gland
⑤
Equipotential bonding conductor
⑥
or
4.6.4.5
Testing the measuring circuit
A simple test with the load cells connected can be carried out with a multimeter.
Note:
In the case of an external load cell supply voltage or use of an isolating unit, the internal
load cell supply is not relevant.
Measuring voltage
0–12 mV = @ LC with 1.0 mV/V
0–24 mV = @ LC with 2.0 mV/V
V
M+
M–
V+
S+
S–
V–
GNDA
V
0 V ±0.5 V
+6 V ±0.4 V
+6 V ±0.4 V
-6 V ±0.4 V
-6 V ±0.4 V
4 Device installation
Process Controller Maxxis 5 PR 5900
Minebea Intec
EN-79