4.6.13
DeviceNet interface
The DeviceNet interface card has the type designation PR 1721/34.
The fieldbus card contains all functionalities to make a complete DeviceNet slave with a
CAN controller and transmission speeds up to 500 kbit/s.
The DeviceNet connection is established by 5-pin terminal
②
.
The card is inserted into "Slot 4"
①
(see Chapter
Technical data
Description
Data
Transfer rate
125, 250 and 500 kbit/s
Protocol
DeviceNet Master Slave
-
Polling procedure (polled IO)
-
CRC error recognition according to IEC 62026 (EN 50325)
-
Max. 64 station nodes
-
Data width max. 512 byte "input & output"
-
Watchdog Timer
④
(see Chapter
)
Configuration
EDS file "sag_5410.eds"
MAC-ID (1
62)
Potential isolation
Yes, optocoupler and DC/DC converter
Bus termination
120
Ω
at the cable ends
Bus load
33 mA @ 24 V DC
Cable type
DeviceNet; color: petrol green; 2x2 twisted pair; screened
X3 Process Indicator PR 5410
4 Device installation
Minebea Intec
EN-104