7.17.7.3
Determining a condition
Additionally, a [Condition] can be assigned to the marker.
The possible conditions are listed in the following table.
Selection list for [conditions]
Function
SPM Bit
Description
no condition
---
No condition
actual diginp1
X00 = 0
digital input 1: not active
actual diginp2
X01 = 0
digital input 2: not active
actual diginp3
X02 = 0
digital input 3: not active
actual limit 1
X16 = 0
Limiting signal 1: not active
actual limit 2
X17 = 0
Limiting signal 2: not active
actual limit 3
X18 = 0
Limiting signal 3: not active
ADC error
X32 = 0
General error in weighing point: not ac-
tive (no error)
above Max
X33 = 0
Weight above Max: not active
overload
X34 = 0
Weight above Max plus the 'overload'
value: not active
below zero
X35 = 0
Weight not below zero
center zero
X36 = 0
Weight not within ¼ d of zero
inside ZSR
X37 = 0
Weight not within zero-setting range
standstill
X38 = 0
Standstill not active
out
X39 = 0
Weight not below zero or above Max
command error
X48 = 0
For internal use only.
command busy
X49 = 0
For internal use only.
A selection window opens.
2.
Select and confirm the appropriate line to set the marker for the corresponding limit
(in this case, Marker 1 is set when 900 g is exceeded).
3.
If applicable, set additional markers and confirm.
X3 Process Indicator PR 5410
7 Commissioning
Minebea Intec