Sequence of [Net decrease] with dosing signals "coarse/fine"
①
Taring:
The current gross weight is saved as the ta-
re and the net weight starts at zero.
②
Coarse:
A coarse flow (coarse and fine) is batched
until the preset value is reached.
③
Fine:
A fine flow is batched until the switch-off
point (overshoot) is reached.
④
Calming:
Time to wait during which the overshoot is
effective and scale vibrations may settle.
⑤
Tolerance checking:
The weight is determined and checked
against the tolerance values.
8.4.1.3
Interaction mode
You can choose between the following control/operating modes of the device in
production:
-
[Remote proc. control] via OPC/ModBus and/or fieldbus
-
[VNC] (Virtual Network Computing)
-
[Front keys]
The following table shows how individual modes are locked when production starts.
Starting production
Mode
Front panel
VNC
Remote control
OPC/ModBus
Remote control
fieldbus
Digital inputs Digital out-
puts
[Remote proc.
control]
✘
✘
✘
✘
[VNC]
✘
✘
[Front keys]
✘
✘
8.4.2
Configuring digital inputs and outputs
SPM addresses are assigned to the digital inputs and outputs under the [Configuration
digital IOs] menu item.
8 Production
X3 Process Indicator PR 5410
EN-257
Minebea Intec