Fieldbus interface
8-Byte
Write window
8-Byte
Read window
Interface
protocol
Data and functions
– Weight data
– Weight status
– Limits
– Digital inputs
– Digital outputs
– Analog output
12.2.1
Write window (input area)
Data are transferred from the master to the slave(PR 5410) in this window.
Byte 0
Write data: MSB
Byte 1
Write data: MSB
Byte 2
Write data: MSB
Byte 3
Write data: LSB
Byte 4
Read_Value_Select
Byte 5
Write_Value_Select
Byte 6
Direct control bits
Byte 7
Direct control bits
The first four bytes are used to write a data value.
The type of the register number of the data is written in byte 5.
In direct access, the bits in bytes 6 and 7 are independent of the write value data type.
The command is executed after a 0-1 transition of the corresponding bit.
12 Fieldbus interface
X3 Process Indicator PR 5410
EN-293