3.5.1
Plug-in cards
The main board can be fitted with max. 2 plug-in cards.
Two cards of the same type must not be plugged into slot 1 and 2 at the same time
(except for PR 5510/04).
If slot 4 has a card, only one other card can be plugged into slot 1 or 2.
Product
Function
Position
PR 5510/02
2 x RS-232 serial
interfaces
The interfaces can be configured by soft-
ware.
For more information, see Chapter
Slot 1 and/or 2
PR 5510/04
-
1 x RS-232 se-
rial interface
-
1 x RS-485/
RS-422 serial
interface
The interfaces can be configured by soft-
ware.
For more information, see Chapter
.
Slot 1 and/or 2
PR 5510/07
Analog input and
output board
Analog input:
internal 14 bits binary = 20,000 counts, @
e.g. 0
20 mA/0
10 V
Analog output:
internal 16 bits = 65,536 parts, resolution
of 20,000 @ 20 mA
For more information, see Chapter
.
Slot 1 or 2
PR 5510/08
BCD output (open
emitter)
Outputs:
5 digits BCD + preceding sign or 3 bytes bi-
nary
Input:
1 bit (DATA IN)
For more information, see Chapter
Slot 1 or 2
PR 5510/09
BCD output (open
collector)
Outputs:
5 digits BCD + preceding sign or 3 bytes bi-
nary
Input:
1 bit (DATA IN)
For more information, see Chapter
.
Slot 1 or 2
PR 5510/12
-
6 digital inputs
-
12 digital out-
puts
6 passive opto-decoupled inputs
12 passive opto-decoupled outputs
The interfaces can be configured by soft-
ware.
For more information, see Chapter
.
Slot 1 or 2
PR 1721/31
ProfiBus-DP
ProfiBus-DP slave acc. to IEC 61158 with
max. 12 Mbit/s
For more information, see Chapter
Slot 4
PR 1721/32
InterBus-S
InterBus-S slave with max. 500 kbit/s
For more information, see Chapter
.
Slot 4
3 Device description
X3 Process Indicator PR 5410
EN-29
Minebea Intec