17
Set the connecting range to DC
・
V for the measuring instrument such as tester
and so on.
Remove the connecting cable for strain gage applied transducer from the terminal board.
Set the connecting range to DC
・
mV range for the measuring instrument such as
tester and so on.
①
Connect the connecting cable for strain gage applied transducer to the terminal board
again. (Refer to the paragraph 3)
②
By checking the voltage between the terminal B and D on the terminal board, apply
load on the strain gage applied transducer.
The voltage between
B and D varies.
The voltage between
A
−
C is DC10 V
3
Make re
−
calibration according to the
procedures in chapter 4
Start measurement
Same condition
YES
NO
YES
YES
NO
NO
Inform
us
about
the
contents
of
failure
and
situation
at
site
in
details.
There may have fears that the
strain gage applied transducer
connected has broken or signal
route (signal wire) has cut off.
Inform
us
about
the
contents
of
failure
and
situation
at
site
in
details.