background image

Batteries

Batteries are the most expensive component of a UPS sys-

tem.  Protect them and extend their life with the Smart Battery 

Management System (SBMS).  SBMS continuously monitors 

battery status and recharges whenever necessary, so you have 

worry-free battery power.

Matching battery cabinets make your CPE look great and allow 

you easy battery access.

Battery Specifications

Battery Run Time Reference (Internal Battery)

Communications Options

Battery Type:      

 

 

 

Sealed Lead Acid Maintenance Free

Quantity (pcs)  (1kVA / 2kVA / 3kVA) 

8

Voltage (VDC) (1kVA / 2kVA / 3kVA) 

36 

72 

96

Recharge Time  

 

 

 

8 hours to 90%

Load 

 

 

1 kVA   

2 kVA   

3 kVA

400VA / 280W 

 

28 Min.   

63 Min.   

96 Min.

800VA / 560W 

 

  9 Min.   

25 Min.   

72 Min.

1000VA / 700W   

  8 Min.   

17 Min.   

24 Min.

1500VA / 1050W   

 

 

10 Min.   

18 Min.

2000VA / 1400W   

 

 

  7 Min.   

14 Min.

2500VA / 1750W   

 

 

 

 

10 Min.

3000VA / 2100W   

 

 

 

 

  8 Min.

Extended 

batteries with 

matching 

cabinets can 

extend run times 

to virtually any 

length of time.

True Relay Card 

 

A 10-pin terminal is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, Battery Bad, UPS 

Alarm, and UPS Shutdown. 

AS/400 Card 

 

A DB9 port is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, and UPS Shutdown. 

WEB/SNMP Card 

 

Integrates multi-network communication protocols to enable comprehensive, easy-to-understand and secure remote monitoring and 

management of the UPS via the Internet. 

www.sizemyups.com

800.238.7272 | 

+1 972.446.7363

MINUTEMAN

®

 CPE

 Series

True On-line UPS Systems