9
8
INSTALLATION PLACEMENT
This UPS series is
ONLY
intended to be installed in an indoor temperature
controlled environment that is free of conductive contaminants. DO NOT oper-
ate the UPS in: extremely dusty and/or unclean areas, locations near heating
devices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Select a location, which will provide good air circulation for the UPS at
all times.
Route power cords so they cannot be walked on or damaged. This
UPS series is not intended for use in a computer room as defined in the
Standard for the Protection of Electronic Computer/Data Processing Equip-
ment ANSI/NFPA 75.
Operating Temperature (Maximum): 0 to 40
°
C (+32 to +104
°
F)
Operating Elevation: 0 to 2,000m (0 to +6,562 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +50°C (+5 to +122°F)
Storage Elevation: 0 to 15,000m (0 to +49,213 ft)
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the UPS system. Place the UPS in the final desired location and complete the
rest of the installation procedure. These UPSs do not have internal batteries
and must be connected to at least one Battery Pack to operate properly. See
the “Rackmount Configuration” to install the UPS into the rack and see the
“Connecting the Battery Pack” procedure to connect the Battery Pack.
USE
CAUTION:
The UPS and Battery Pack are extremely heavy. Use the appro-
priate number of personnel when installing the UPS system.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS.
The mounting brackets are
ONLY
for securing the UPS to the rack.
1. The Parallel port is used for communication between two UPSs and the
Maintenance Bypass Switch (MTBS) for parallel operation.
2. The Charger Detection port connects to an external charger.
3. The RS232 communications port is for UPS monitoring and control.
4. The Smart slot is used for mini option cards.
5. The Input Circuit Breaker will trip in the event the load exceeds the UPS’s
power rating.
6. The Input Terminal Block is for connecting the input utility power.
7. The Output Terminal Block is for connecting the load.
8. The External Battery Connector is for connecting the Battery Packs.
9. The Fan provides airflow for the UPS.
10. The Remote Control port is used to remotely shutdown the UPS.
11. The SNMP slot is used for option cards.
REAR PANELS
Chapter 3: Installation
NOTE:
If you are using more than one Battery Pack with this UPS series, the
UPS must be configured so that the UPS will report the correct estimated
runtime on the LCD screen and in the Power Monitoring software and/or the
SNMP card. See the Power Monitoring software or the SNMP card’s User’s
Manual to configure the UPS.