Thank you for purchasing this power protection product.  It has been designed
and manufactured to provide many years of trouble free service.  Please read
this manual before installing your Entrepid Series UPS, models ETR550LCD,
ETR700LCD, ETR1000LCD, ETR1500LCD as it provides important informa-
tion that should be followed during the installation and the maintenance of the
UPS system allowing you to correctly set up your system for the maximum
safety and performance.  Included is information on customer support and
factory service, if it is required.  If you experience a problem with the UPS
system please refer to the Troubleshooting guide in this manual to correct the
problem or collect enough information so that the Technical Support Depart-
ment can assist you.

CAUTION!

  The maximum ambient operating temperature for this UPS series

is 40°C (“0 ~ 40°C” for Ambient Operation).

The external vents and openings on the UPS are provided for ventilation.
To ensure reliable operation of the UPS and to protect the UPS from over-
heating, these vents and openings must not be blocked or covered. Do not
insert any object into any of the vents or openings that may hinder the ve-
ntilation.

Install the UPS system in a well ventilated area, away from excess moistu-
re, heat, dust, flammable gas or explosives.

Leave adequate space (at least 20cm) around all sides of the UPS system
for proper ventilation.

Do not mount the UPS system with its front or rear panel facing down at
any angle.

 Before usage, you must allow the UPS system to adjust to room temper-

ature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture
condensing inside the UPS.

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS !

CONSIGNES DE SÉCURITÉ IMPORTANTES

SAUVEGARDEZ CES CONSIGNES!

Chapter 1:  Introduction

WARNING:

  

Risk of Electrical Shock.  Hazardous live parts inside these

power supplies are energized from the battery even when the AC input is
disconnected.

CAUTION!  

To de-energize the outputs of the UPS:

1.

If the UPS is on press and release the On/Off/Test Button.

2.

Disconnect the UPS from the AC wall outlet.

3.

To de-energize the UPS completely, disconnect the battery.

CAUTION!

 

 To reduce the risk of electrical shock in conditions where the

load equipment grounding cannot be verified, disconnect the UPS from the
AC wall outlet before installing a computer interface cable.  Reconnect the
power cord only after all signaling connections are made.

CAUTION!  

Connect the UPS to a two pole, three wire grounding AC wall

outlet.  The receptacle must be connected to the appropriate branch protec-
tion (circuit breaker or fuse).  Connection to any other type of receptacle may
result in a shock hazard and violate local electrical codes.  Do not use exten-
sion cords, adapter plugs, or surge strips.

CAUTION!  

To reduce the risk of electrical shock with the installation of this

UPS equipment and the connected equipment, the user must ensure that the
combined sum of the AC leakage current does not exceed 3.5mA.

WARNING:

  

This Uninterruptible Power Supply contains potentially hazard-

ous voltages.  Do not attempt to disassemble the UPS beyond the battery
replacement procedure.  This UPS contains no user serviceable parts.  Re-
pairs and Battery replacement must be performed by

 QUALIFIED SERVICE

PERSONNEL ONLY.

CAUTION!

  To reduce the risk of fire, connect only to a circuit provided with

20 amperes maximum branch circuit over-current protection in accordance
with the National Electric Code, ANSI/NFPA 70.

WARNING:  Qualified Service Personnel ONLY 

must perform the Installa-

tion and Servicing of these UPS systems.  MINUTEMAN accepts no liabilities
and is not limited to: injury to the Service Personnel, or damages to; the UPS,
or the connected equipment caused by the incorrect installation or servicing
of the UPS system.

Veuillez lire ce manuel avant l'installation de l'onduleur modèles ETR550LCD,
ETR700LCD, ETR1000LCD, ETR1500LCD. Il contient de l'information
importante qui doit être respectée au cours de l'installation et de l'entretien de
l'onduleur et des batteries. Cette information vous permettra de correctement
installer le système pour atteindre son rendement maximum en toute sécurité.

CAUTION!

  This UPS series is 

ONLY

 intended to be installed in an indoor

temperature controlled environment that is free of conductive contaminants.
This UPS series is not intended for use in a computer room as defined in the
Standard for the Protection of Electronic Computer/Data Processing Equip-
ment ANSI/NFPA 75.

Summary of Contents for ETR1000LCD

Page 1: ...User s Manual Entrust LCD Series UPS Para Systems Inc 1455 LeMay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000493 R2x...

Page 2: ...rols and Indicators 6 3 Installation 9 4 Operation 12 5 Troubleshooting 15 6 Replacing the Battery 16 7 Obtaining Service 19 8 Specifications 20 9 Limited Product Warranty 22 A1 Declaration of Conform...

Page 3: ...the battery CAUTION To reduce the risk of electrical shock in conditions where the load equipment grounding cannot be verified disconnect the UPS from the AC wall outlet before installing a computer...

Page 4: ...to correct the interference by one or more of the following measures Reorient the receiving antenna Relocate the computer with respect to the receiver Move the computer away from the receiver Plug th...

Page 5: ...UPS will sound a constant alarm to indicate that there is an Overload condi tion Battery Capacity Bar Graph Displays the amount of Battery Ca pacity available in the AC and Battery mode as 20 40 60 80...

Page 6: ...cement and all the cautions before installing the UPS Place the UPS in the final desired location and complete the rest of the installation procedure These UPSs are shipped with the internal batteries...

Page 7: ...the UPS Use only the interface cable that come with these UPSs The USB communications protocol is HID The HID USB driver comes standard in the Windows OS Simply connect the USB cable to the USB commun...

Page 8: ...release TEST BUTTON To perform a ten second user invoked battery test With the UPS in theAC normal mode press and hold the On Off Test Button until the alarm sounds four beeps and then release During...

Page 9: ...yed on the LCD screen the alarm will sound continu ously and the output will be turned off The fault condition in some instances may be cleared by turning the UPS off and then on If the fault conditio...

Page 10: ...re attempting to ser vice the batteries Typical battery life is 3 to 5 years Environmental factors do affect battery life High temperatures poor utility power and frequent short duration discharges ha...

Page 11: ...f the model information about your unit d The serial number of your unit e Any information on the failure including LEDs that may be illuminated or error codes displayed f A description of the protect...

Page 12: ...hutdown Immediately Chapter 8 Specifications BATTERY SYSTEM Typical Recharge Time Typical Battery Life 3 to 5 years Environmental factors do affect battery life High temperatures poor utility power an...

Page 13: ...RANTIES EX PRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITYAND FIT NESS FORAPARTICULAR PURPOSE Some states do not permit limitation of implied warranties therefore the aforesaid limitation s...

Page 14: ...25 24 Notes Notes...