9
8
Output Power Receptacles
NEMA 5-15P W/6 ft cord
Model #
Input Power Plug
ETR1000LCD
ETR1500LCD
4-NEMA 5-15R Battery Backup & Surge
4-NEMA 5-15R Surge Only
REAR PANEL
1. Input power cord: Connecting to Utility Power.
2. Surge-only output receptacles: Noncritical equipment.
3. USB Communications Port: UPS monitoring and control.
4. Battery Backup & Surge output receptacles: Mission critical equipment.
5. 550/700: Vent only. 1000/1500: Vent and fan.
6. Input circuit breaker: Protection against an excessive overload.
5-NEMA 5-15R Battery Backup & Surge
5-NEMA 5-15R Surge Only
ETR550LCD
ETR700LCD
NEMA 5-15P W/6 ft cord
CONNECTING THE BATTERIES
(QUALIFIED
SERVICE PERSONNEL ONLY)
Please read all of the
WARNINGS
and
CAUTIONS
before attempting to connect
the batteries.
1.
Use
CAUTION
, the UPS is heavy.
Remove the UPS from the shipping box
and set on a desk or a bench top.
NOTE:
No tools are required for removing or installing the front panel.
2. Slide the front panel downward, then outward, and then set it aside. (FIG. 1)
3. Verify proper polarity. Connect the battery connectors together. (FIG 2)
NOTE:
Some sparking might occur this is normal.
4. Reinstall the front panel onto the UPS.
5. Continue with the rest of the Installation.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing the
UPS. Place the UPS in the final desired location and complete the rest of the
installation procedure. These UPSs are shipped with the internal batteries discon-
nected. The batteries must be connected before putting these UPSs into service.
See Connecting the Batteries to connect the batteries.
INSTALLATION PLACEMENT
This UPS series is
ONLY
intended to be install in an indoor temperature controlled
environment that is free of conductive contaminants. DO NOT operate the UPS in:
extremely dusty and/or unclean areas, locations near heating devices, water or ex-
cessive humidity, or where the UPS is exposed to direct sunlight. Select a location,
which will provide good air circulation for the UPS at all times.
Route power cords
so they cannot be walked on or damaged.
Typical battery life is 3 to 5 years. Envi-
ronmental factors do affect battery life. High temperatures, poor utility power, and
frequent, short duration discharges have a negative impact on battery life. This
UPS series is not intended for use in a computer room as defined in the Standard
for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA
75.
Operating Temperature (Maximum): 0 to 40
°
C (+32 to +104
°
F)
Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +50°C (+5 to +122°F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
Chapter 3: Installation