15
14
WEAK/BAD BATTERY
The UPS automatically tests the battery’s condition. If the battery is weak, bad
or disconnected, the Weak/Bad Battery icon will illuminate and the Battery
Capacity Bar Graph will turn off and the alarm will sound three beeps every
five minutes until the battery is either reconnected or replaced. This alarm will
be repeated until the batteries pass a self-test. It is recommended that the
UPS be allowed to charge overnight before performing a battery test to con-
firm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
Overload icon will illuminate and the alarm will sound continuously (AC and
Battery modes). This alarm will remain on until the excess load is removed or
the UPS’s self protection circuit shuts the UPS down.
To clear the overload alarm when the UPS has shutdown requires that the UPS
perform a battery test. First remove part of the load, then turn the UPS on, the
Overload icon and the alarm will be on. Second either use the Test Button or
unplug the input power cord to perform the battery test.
ALARMS
ON BATTERY
When the UPS is operating on the batteries, the AC normal icon will extinguish,
the On-Battery icon will illuminate, the LCD will display the estimated runtime
remaining and the alarm will sound one beep every 10 seconds. Once the
UPS returns to the normal AC mode, the alarm will stop, the On-Battery icon
will extinguish and the AC normal icon will illuminate.
LOW BATTERY WARNING
When the batteries reach the predetermined level, the alarm will sound two
beeps every five seconds, the Battery Bar Graph will display the remaining
battery capacity and the LCD will display error code E07. This information is
to inform the user that there is approximately two minutes of runtime remaining
before the UPS shuts down. This condition will continue until either AC returns
or the UPS’s self protection circuit shuts the UPS down to protect the battery
from over discharging.
UPS FAULT
When the UPS detects an internal fault, the Fault icon will illuminated and an
error code will be displayed on the LCD screen, the alarm will sound continu-
ously and the output will be turned off. The fault condition, in some instances,
may be cleared by turning the UPS off and then on. If the fault condition does
not clear the UPS must be sent in for service. See the Troubleshooting sec-
tion.
Chapter 5: Troubleshooting
Error Code: E01. UPS
is shutdown.
Symptom / Error Code
Cause / What To Do
Press the On/Off/Test button and release after one
beep.
UPS will not turn on.
Reset the input circuit breaker by pressing the
plunger back in. If the input circuit breaker trips af-
ter UPS restarts, reduce the load on the UPS.
UPS operates in battery
mode only, even though
there is AC present.
The AC normal icon is
illuminated, but there is
no output.
Disconnect the computer cable from the UPS, press
the On button. If UPS works normally, the software
has control of the UPS.
Charge the batteries for 8-hours and retest. If the
runtime is still less than expected, the batteries may
need to be replaced.
UPS does not provide
expected runtime.
The AC Normal icon is
blinking and the alarm
is silent.
The UPS is in Boost mode. It is performing its in-
tended function.
The UPS has an internal problem. Call for service.
Fault icon is illuminated
and a constant alarm.
Error Code: E02.
Overload icon is illumi-
nated and a constant
alarm.
Check the specifications and remove part of the load.
If the UPS shuts down because of an Overload, the
UPS must perform an Inverter function or a Self Test
to clear the Overload Alarm.
The UPS has detected a short-circuit on its output.
Check the attached load.
Error Code: E04: In-
verter/Output Failure
Shutdown.
The UPS has an internal fault. Call for service.
Error Code: E05. Charger
Failure Warning.
The charger has failed, call for service.
Error Code: E08. SWF
icon is illuminated.
Have a qualified electrician correct the service
wiring.
Error Code: E06.
Weak/Bad Battery icon
is illuminated.
Check the battery connections, charge the batteries
for 8-hours and retest, or replace the batteries.
Error Code: E07. Low
Battery Warning.
The UPS's battery reserve is low. This condition will
continue until AC returns or the UPS shuts down from
battery exhaustion.
Error Code: E03. Over
Temperature Shut-
down.
The internal or ambient temperature has exceeded
the safe operating range for the UPS. Check the
specifications.
Summary of Contents for ETR1000LCD
Page 14: ...25 24 Notes Notes...