SPECIFICATIONS
Model
MM-AVR 600
MM-AVR 800
MM-AVR 1200
Capacity
600VA/300W
800VA/480W
1200VA/600W
Phase
Single phase
Voltage Range
95V-145V ±3V
Input
Frequency
60HZ ±5HZ
Voltage
(battery mode)
120V ±10%
Waveform
AC mode - follow utility
Battery mode - Step Sine Wave
Frequency
AC mode - follow utility, Battery mode - 60Hz ±5Hz
Frequency
<0.5HZ (battery operation)
Output
Transfer Time
Typical 4ms, max 10ms
Surge Protection
320 Joules
Input Protection
Compliance with IEEE 587
Protection
Short Circuit
Fuse
Type
12V Sealed non-spillable lead acid, maintenance free
Recharge
After full discharge, 8 hours to 90% capacity
Backup Time
(full load)
≥
3 min
Charge Current
350mA
~
1A
Battery
Battery
Configuration
1x12V/7AH
1x12V/9AH
2x12V/7AH
AC Mode
Green and Orange LED on, Red LED off,
No Alarm
Charging Battery
Orange LED on
Battery Mode
Green and Orange LED off, Red LED flash,
Alarm slow beep
Indication
Battery Low
Green and Orange LED off, Red LED flash,
Alarm fast beep
Audible Noise
at 1 m (3 ft)
<45dB
Temperature
0 to 40
°
C (+32 to +104
°
F)
Environment
Humidity
0% - 90% Non- Condensing