13
Pro Series
Date of manufacture
1826
Enabled
Enabled
UPS output
92 VAC (176 for 230
VAC models)
Use this function to uniquely
identify the UPS in your net-
work configuration
Enter the current date when
replacing batteries
When enabled, the UPS will
automatically restart from a
low battery shutdown when
normal A/C returns
Enabled - the UPS will emit a
short beep when in the bat-
tery mode. At Low Battery the
UPS will emit a steady tone
only at low battery warning
through shutdown.
Disabled - Use only when
software is controlling the
UPS or to silence the alarm
UPS Output - When the UPS
is told to shut down, it turns
off the UPS output only. UPS
- Turns off the UPS which re-
quires the UPS to be turned
on manually
Changes the voltage point at
which the UPS switches to
battery power
(These items require optional software or hardware)
FUNCTION
FACTORY DEFAULT
DESCRIPTION
Up to 64 characters to
define the UPS
Date of battery replace-
ment -
day/month/year
XX/XX/XXXX
Up to 5 characters
Enable or disable
Enabled, at low battery,
disabled
UPS output or UPS
92 or 88 VAC (176 or
166 VAC for 230 VAC
models)
USER CHOICES
UPS ID
Battery install
date
Battery life in
days
Enable/Disable
auto resstart
Set audible
alarm state
Shutdown
Type
Set low voltage
Xfer point
9
At first battery replacement,
reset to reflect actual number
of days experience in your
environment or leave factory
default.
CON
FIGURABLE PARAMETERS
& SETTINGS
English