34
designated maximum mixed water outlet temperature setting of the valve.
Temperature readings should be taken at the normal flow rate after allowing for the
system to stabilise.
The sensing part of the thermometer probe must be fully submerged in the water
that is to be tested.
Any TMV that has been adjusted or serviced must be re-commissioned and re-tested
in accordance with the instructions given in this guide.
The installation of thermostatic mixing valves must comply with the requirements of
the Water Supply (Water Fittings) Regulations 1999.