TYPE 2 VALVES

Application

The approved designations for Type 2 Valves 

are as follows:

Models

Designation

Mira Element SLT

LP-S, HP-S

Important!  The  fitting  of  any  flow  regulator 

will invalidate TMV2 compliance due to the 

minimum  flow  rate  requirements.  Do  not  fit 

flow regulators in TMV2 applications.

Conditions of use for Type 2 Valves

Operating Pressure 

Range

High 

Pressure

Low 

Pressure

Maximum Static 

Pressure (bar)

10

10

Maintained Pressure, 

Hot and Cold (bar)

0.5 to 5

0.1 to 1

Hot Supply 

Temperature (°C)

55 to 65

55 to 65

Cold Supply 

Temperature (°C)

≤25

≤25

Valves operating outside these conditions cannot 

be guaranteed to operate as Type 2 Valves.

Recommended Outlet Temperatures

The BuildCert TMV scheme recommends the 

following set maximum mixed water outlet 

temperatures for use in all premises:
44°C for bath fill, but see notes below;
41°C for showers;
41°C for washbasins;
38°C for bidets.
The mixed water temperatures must never 

exceed 46°C.
The maximum mixed water temperature can be 

2°C above the recommended maximum set outlet 

temperatures.

Note! 

46°C is the maximum mixed water 

temperature from the bath tap. The maximum 

temperature takes account of the allowable 

temperature tolerances inherent in thermostatic 

mixing valves and temperature losses in metal 

baths.

It is not a safe bathing temperature for adults 

or children.

The British Burns Association recommends 37 

to 37.5°C as a comfortable bathing temperature 

for children. In premises covered by the Care 

Standards Act 2000, the maximum mixed water 

outlet temperature is 43°C.

The thermostatic mixing valve will be installed in 

such a position that maintenance of the TMV and 

its valves and the commissioning and testing of 

the TMV can be undertaken.

The fitting of isolation valves is required as close 

as practicable to the water supply inlets of the 

thermostatic mixing valve.

Commissioning notes for Thermostatic Mixing 

Valves

The  first  step  in  commissioning  a  thermostatic 

mixing valve is to check the following:
The designation of the thermostatic mixing valve 

matches the application.
The supply pressures are within the valves 

operating range.
The supply temperatures are within the valves 

operating valve.
Isolating  valves  (and  strainers  preferred)  are 

provided.
If all of these conditions are met, proceed to 

set the temperature as specified in section: 

‘Commissioning’

.

Important! 

The mixed water temperature at the 

discharge point must never exceed 46°C

Summary of Contents for Element SLT

Page 1: ...1 MIRA ELEMENT SLT INSTALLATION AND USER GUIDE THERMOSTATIC MIXER These instructions must be left with the user...

Page 2: ...ngle lever for on off and temperature control A Mid Flow Overide feature allows up to 30 reduction in flow at low pressures and a Temperature Overide warns when moving into a hotter temperature zone A...

Page 3: ...commissioned operatedand maintained in accordance with manufacturer s recommendations 2 Type 2 Valves are only used for applications covered by their approved designations refer to section Type 2 Valv...

Page 4: ...1 x 2 5 mm Hexagonal Key q 1 x 2 5 mm Hexagonal Key q 1 x Multi Tool q 1 x Multi Tool q 1 x 14 L Min Flow Regulator q 1 x 14 L Min Flow Regulator q 2 x Securing Brackets q 4 x Bracket Securing Screws...

Page 5: ...could detrimentally affect thermostatic performance For safety and performance reasons it is recommended that the maximum hot water temperature is limited to 65 C Cold Water Range up to 25 C Minimum...

Page 6: ...6 All dimensions in mm Built in Thermostatic Mixer 153 56 116 142 35 62 183 108 30 59 80 Building in Depth 45 56 Exposed Thermostatic Mixer Dimensions...

Page 7: ...y Regulations 1999 Water Fittings or any particular regulations and practices specified by the local water company or water undertakers Note Make sure that all site requirements correspond to the info...

Page 8: ...r solid walls drill the holes for the backplate with a 6 mm diameter drill and insert the wall plugs Note For other types of wall structure alternative fixings may be required not supplied Wall Plug 4...

Page 9: ...the backplate to the wall using the screws 8 For Rear Entry Supplies Only Fit the concealing plates over the inlet pipes Note Apply silicone sealant to the back face of the flange Apply Silicone Seal...

Page 10: ...upplied Remove the elbows and install on opposite sides Retighten the grubscrews Caution Do not overtighten Note Make sure that the O seals are correctly fitted and that the filter caps can be accesse...

Page 11: ...mponents will not fit correctly then mark the positions of the fixing screw holes on the wall 7 For solid walls drill two 6 mm holes for the wall plugs 8 Fit the hot and cold supply pipes Hot Left Col...

Page 12: ...r Plugs are positioned so that they can be removed for servicing 5 Drill the two 5 5 mm holes for the fixing positions countersink the holes at the front 6 Fit the hot and cold supply pipes Hot Left C...

Page 13: ...6 mm holes for the wall plugs Caution Do not drill into pipes in the wall 6 Fit the hot and cold supply pipework Hot Left Cold Right 7 Caution It is essential at this point that the supply pipework is...

Page 14: ...rill four 6 mm holes for the wall plugs For other types of wall structure alternative fixings may be required not supplied 17 Insert the wall plugs and attach the concealing ring to the wall with the...

Page 15: ...wall surface by 21 23 mm Note Remove any burrs from the pipes before proceeding 4 For solid wall installations or stud partition installations without rear access go to build instruction 9 For stud pa...

Page 16: ...1 This completes the installation of the RAC assembly Dome Shroud Chrome Trim Built in models only Dome Clamp Bearing Bracket Securing Screw REVERSED INLET SUPPLIES The Mira Element SLT thermostatic m...

Page 17: ...nsert was originally removed from pushing the hinge pin in from right to left 13 Make sure that the two cartridge inlet seals are fitted and carefully push the cartridge into the body aligning the car...

Page 18: ...dge and engage with the temperature adjusting screw 4 Rotate the hexagon key until the required maximum temperature is obtained at the shower Turn anticlockwise to increase the temperature or clockwis...

Page 19: ...tap The maximum temperature takes account of the allowable temperature tolerances inherent in thermostatic mixing valves and temperature losses in metal baths It is not a safe bathing temperature for...

Page 20: ...ter that is to be tested Any TMV that has been adjusted or serviced must be re commissioned and re tested in accordance with the instructions given in this guide The installation of thermostatic mixin...

Page 21: ...ted or plastic fittings Do not use descalents on this product Inlet Filters The inlet filters should be checked and cleaned as necessary every 12 months Note The inlet filters must not be removed exce...

Page 22: ...mm hexagonal wrench and remove the filters Note Use pliers to carefully remove the filters 6 Clean each of the filters under a jet of water to remove any lodged particles 7 Refit the filters and tight...

Page 23: ...nnector Pack 1663 265 Flow Regulator Pack 1656 114 Elbow Connector Pack 1656 112 Elbow Assembly 1656 111 Elbow Cap 1062477 Filter Pack x2 1656 113 Backplate 1656 117 Inlet Connector Pack 1656 110 Seal...

Page 24: ...B 1595 066 Filter Pack x2 1595 046 Seal Pack Identified A 1656 168 Screw Pack Identified B 1595 150 Elbow Assembly Both sides A 1656 167 Trim Pack 1656 161 Overide Pack A 1656 160 Cartridge Assembly...

Page 25: ...25 RAC Assembly 1617 171 RAC Shroud 450 20 RAC Mounting Pack 450 20 RAC Mounting Pack 1663 265 Flow Regulator Pack...

Page 26: ...DCV H Chrome 1 0 110 55 1 DCV H An outlet double check valve designed to prevent the backflow or backsiphonage of potentially contaminated water through shower controls which are fitted with a flexib...

Page 27: ...27 NOTES...

Page 28: ...d If you require further assistance call our Customer Services Team Extended Guarantees A selection of protection plans are available that enable you to cover repair bills for the life of your policy...

Reviews: