Using the Configurator
167
If the number of loop controllers that you selected exceeds the maximum number of loop
controllers allowed on this node, an error message appears saying that the Configurator
cannot add some of the CPUs.
7. Click
Close
.
See the loop controller
1. Click the loop controller in the Job Tree.
Figure 129 Loop Controller
Type
Conventional Adder or Loop Adder.
Daughter board installed
Select this check box if the quad loop adder’s daughter
board is installed.
Tag
Type a description for the loop controller.
CPU Number
Select the CPU address for the loop controller.
Overrides
These options override the options on the Job Details
page.
CLIP/Advanced Protocol
Address Space
Defines the address boundary between CLIP devices and
Advanced Protocol devices.
•
AP Start:
Enter the starting address of the AP
devices on the loop. The address space below this
entry is allocated for CLIP devices and the address
space above and including this entry is allocated for
AP devices. Valid AP Start values are 001 to 100.