QAZT-5348DS and QAZT-5302DS Network Firefighters’ Telephone Selector Panel
118
QAZT- 5348DS and QAZT- 5302DS Netw ork Firefighters’
Telephone Selector Panel
Figure 84: QAZT- 5348DS and QAZT- 5302DS Netw ork Firefighters' Telephone
Selector Panel
Each QAZT-5348DS annunciates and
controls up to 48 telephone zones. Each
QAZT-5302DS annunciates and controls
up to 24 telephone zones. There is one
button and two LEDs per zone. The
lower amber LED indicates zone trouble.
The upper green LED indicates whether
that zone is selected for telephone
communication.
Telephone zone selection buttons toggle
ON and OFF telephone communication
for that zone.
Connect the first QAZT-5348DS Network Firefighters’ Telephone Selector panel to the master telephone by
connecting P1 cable into P2 on the QMT-5302N/V Master Telephone. P4 of the QAZT-5348DS is connected to P1 of
the next display panel (up to six total).
Connect the first QAZT-5302DS Network Firefighters’ Telephone Selector panel to the master telephone by
connecting P1 cable into P2 on the QMT-5302N/V Master Telephone. P2 of the QAZT-5302DS is connected to P1 of
the next display panel (up to six total).
Note:
Use configurator to set up the QAZT-5348DS and QAZT-5302DS Telephone Zone Selector Panels
.
Telephone
#1
Telephone
#2
Telephone
#3
Telephone
#4
Telephone
#5
Telephone
#6
Telephone
#7
Telephone
#8
Telephone
#9
Telephone
#10
Telephone
#11
Telephone
#12
Telephone
#13
Telephone
#14
Telephone
#15
Telephone
#16
Telephone
#17
Telephone
#18
Telephone
#19
Telephone
#20
Telephone
#21
Telephone
#22
Telephone
#23
Telephone