FleX-Net
TM
Installation and Operation Manual
119
Figure 85: QAZT- 5348DS Telephone Selector Board
QAZT-5302DS can be used as a telephone or paging selector panel by installing a jumper, see diagram below.
Figure 86:
QAZT- 5302DS Telephone Selector Board
Connect the first QAZT-5302DS Network Firefighters’ Telephone Selector panel to the master telephone by
connecting the Ribbon In cable into P2 on the QMT-5302N/NV Master Telephone. Ribbon Out cable to the Ribbon
In of the next QAZT-5302DS or P1 of the next display panel (up to six total). See diagram below.
QAZT-5302DS can be used as a telephone or paging selector panel by installing a jumper, see diagram below.
Note:
All modules such as QMP-5101N/ NV Network Master Paging Control Module, the QMT-5302N/ NV
Network Master Firefighters’ Telephone Control Module, the I PS-4848DS, I PS-2424DS display
modules and the paging or telephone selector panels QAZT-5348DS, QAZT-5302DS are daisy
chained together starting from the FX-2000N LCD display module, DSPL-420(DS), DSPL-2440, RAXN-
LCD or RAXN-LCDG. Total number of boards allowed in the daisy chain connection is 6 (12 frames).
P4
P1
Ribbon Cable connects
here on QAZT-5348DS and
connects to the next
display module Ribbon IN
Ribbon Cable is permanently
attached here and connects to
previous Ribbon OUT connector
Install Jumper for QZP
Ribbon Cable is permanently attached
here and connects to Ribbon OUT con-
nector of Master Telephone, Master
Paging Microphone or previous QAZT-
5302DS.
Install jumper here
to use QAZT-5302DS
as a paging zone
selector panel.
Ribbon Cable connects here on QAZT-5302DS and goes to
the next QAZT-5302DS or display module, Ribbon IN.