Hardw ire Relay Adder Module ( RM- 1008A)
Figure 22: Hardw ire Relay Adder Module ( RM- 1008A)
P2:
Data cable to P6 or P5 of main fire alarm module, or to previous adder module.
P1:
Data connector for next adder module.
P4:
Power connector to P8 of main fire alarm module, or to previous adder module.
P3:
Power connector for next adder module.
JW1:
Remove continuity jumper if there are any more adder modules installed. If this is the last module installed, leave JW1 on.
JP1-JP8:
Move jumpers from pins 1 and 2 to 2 and 3 to connect relay commons between two or more relays.
Polarity Reversal and City Tie Module ( Model PR- 300)
Figure 23: Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
Table 6: PR-300 jumper settings
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active (Not allowed by UL 864
refer to Configuration section). This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals
will resound and the City Tie Box will be retriggered. Please refer to the Configurator for more information.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail. Please refer to the Configurator for more
information.
P1
Cable connects to
P4
on the
FX-2000N Main Fire Alarm Board
P2
Not used. If a UDACT-300A is used in conjunction with a PR-300, then the UDACT-300A
ribbon cable P1 is connected to header P2 of the PR-300.
JW4
Jumper JW4 is always left intact.
Note:
Jumper JW4 on the FX-2000N main fire alarm board must be removed if a city tie module is installed.
P1
P3
P4
FIELD WIRING TERMINALS
P2
JW1
FIELD WIRING TERMINALS
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
I1
I2
I3
I4
I5
I6
I7
I8
POLAR
IT
Y
RE
VE
RSA
L
ALAR
M
POLAR
IT
Y
RE
VE
RSA
L
SU
P
V
CI
TY
TI
E
+ | -
+ | -
+ | -
JW4
P1 P2
Mounting hole for
#6-32 screws
Mounting hole for
#6-32 screws