FleX-Net
TM
Installation and Operation Manual
45
Analog Loop Wiring
Figure 29: Loop Terminal Connections - Class B
Notes:
• Terminal blocks are “depluggable” for ease of wiring.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power limited and fully
supervised.
• Observe in and out polarity when using module and base isolators.
ANALOG
LOOP
CONNECTIONS
FX-2000N
C
s
H
LEGEND
Addressable Smoke Detector
with Standard Analog Base
Addressable Thermal Sensor
with Standard Analog Base
Conventional Smoke Sensor
Addressable Manual
Pull Station
Combination
Horn/ Strobe
Addressable
Monitor Module
(Wire Class B only)
Addressable Supvr.
Output Module
End-Of-Line-Resistor
F
S
SO
2 Pair
4-WIRE
RESETTABLE
SUPPLY
+
+
+
-
-
-
F
S
L
OOP
2
S
C
s
H
S
S
TWISTED PAIR WIRE
TWO WIRES
B
A
+
-
+
-
C
s
C
s
C
s
F
F
H
H
M
M
SO
M
Conventional Heat Sensors
and Manual Pull Stations
MAIN FIRE ALARM BOARD
INDICATING
CIRCUIT
NAC 0