FleX-Net
TM
Installation and Operation Manual
65
System Reset Button
The System Reset button causes the Fire Alarm Control Panel, and all Circuits, to be reset
• Resets all Latching, Trouble Conditions
• Resets all Initiating Circuits
• Resets 4-Wire Smoke Supply and Aux. Power Supply
• Turns off all NACs
• Turns off Signal Silence, Ack & GA Indicators
• Turns off Fire Drill
• Stops and resets all Timers
• Processes inputs as new events
• Aux Disconnect is not affected
• Reset cannot be activated until the Signal Silence Inhibit timer has expired.
Signal Silence Button
Activation of the Signal Silence button when the Panel is in Alarm, turns on the Signal Silence Indicator and
deactivates any Silenceable NACs. Non-Silenceable Circuits are unaffected. Signals will re-sound upon any
subsequent Alarm. This button does not function during any configured Signal Silence Inhibit Timer period. It also
does not function if the NACs are active as the result of a Fire Drill. In a Two Stage System, if the Auto General
Alarm Timer has timed out, this Signal Silence button also performs the same function as the
Automatic Alm Sig
Stop (Ack)
button.
Fire Drill Button
The Fire Drill button activates all programmed and non-Disconnected NACs, but does not transmit any Alarms via
the City Tie, or Common Alarm Relay. Fire Drill may be programmed to operate specific NACs. Fire Drill is
cancelled by pressing the button again (toggle switch), or if the Panel goes into a real Alarm.
Automatic Alm Sig Stop ( ACK) or General Alarm Cancel Button ( Tw o Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is configured for Two
Stage Operation, activation of the
Automatic Alm Sig Stop (Ack)
button while the Auto General Alarm Timer is
timing (there is an Alarm in the Panel, but it is still in the First Stage), that timer is cancelled, and the
Automatic
Alm Sig Stop (Ack)
Indicator is on steady amber.
General Alarm Button
Activation of the General Alarm button immediately sends the Panel into General Alarm. It will also re-activate the
Signals if they have been Silenced during General Alarm. The General Alarm condition remains active until the
Panel is reset.
Lamp Test Button
Activation of the Lamp Test button turns all front panel Indicators on steady in whichever colour they would
normally be activated and turns the buzzer on steady. If Lamp Test is active for more than 10 seconds, Common
Trouble is activated.