70
Evacuation Codes
Single stage codes
Tw o-stage codes
:
Figure 44: Evacuation Codes
Continuous
On 100% of the time
Temporal Code
3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code
0.5 second on, 0.5 second off
California Code
5 seconds on, 10 seconds off
Alert Code
0.5 second on, 2.5 seconds off
General Alarm
Evacuation code as selected from above.
0.5s
0.5s
1.5s
0.5s
0.5s
5s
10s
CONTI NOUS
TEMPORAL CODE
MARCH CODE
CALI FORNI A CODE
0.5s
2.5s
ALERT CODE
CONTINUOUS