3
•
The FleX-Net
™
is compatible with COPTIR, Pinnacle, Acclimate and 4-20mA devices.
•
Configuration options are provided for grouping inputs.
•
Panel supports previous, current and next configuration. Configuration automatically
reverts back to previous or moves to future configuration through front-panel menu.
•
OPEN Graphic Navigator Software Package (OpenGN) allows 3D graphic display of
premises and devices. Use the Ethernet port on the main board to connect to OpenGN
graphics software.
•
Boolean logic functions are now available within the configuration software.
•
Allows a choice of multiple configuration files to support site-specific requirements.
•
The FleXBoot
™
shell offers UNIX style commands for directory listing, log download,
diagnostic probing and system tuning and optimization.
1.1.2 Overall Audio Features:
•
Supervises signal circuits while in use.
•
Control of fire management operations (e.g. all-call paging and total evacuation
signalling).
•
Indication of all required fault conditions.
•
Microprocessor-based operations with hardware and software watchdog timer to ensure
reliable system operation.
•
Supervised tone generators.
•
Up to 100 audio zones per node, 4788 audio amplifiers per Network system.
•
Up to 5 (analog) firefighters’ telephone zones per node and 315 (analog) telephone
zones per Network system. 99 addressable telephone zones per loop, maximum of 29
addressable telephone loops per node, maximum of 144 addressable telephone zones
per system.
•
Operates from 24 VDC backup batteries in the event of a power failure.
•
Removable terminal blocks for ease of installation and maintenance.
•
Speaker circuits integrated with amplifier circuits.
•
Maximum of 100 Watts per amplifier.
•
Maximum of 575 Watts per expansion cabinet.
•
Supports up to 10 audio cabinets (1 main plus 9 expansion audio cabinets)
•
Each expansion audio cabinet up to 2000 feet.
•
Optional redundant backup amplifier per node.
•
Multi-channel playback.
•
Auxiliary Audio Input with amplifier supervision during non-fire use.
•
Optional remote supervised splitters for separate corridor and room silencing.
•
Each amplifier can play back on a separate audio channel.
•
Each amplifier can be Class A and Class B field wired.
Summary of Contents for FX-MNS-6000