112
17.2
ANC-6000 Audio Network Controller Board Address Setting (DIP SWITCH SW1)
17.3
ACN-792MISO Loop Adder Module (CPU) Address Setting (DIP SWITCH SW1)
17.4
RAXN-LCD/RAXN-LCDG Remote Annunciator Address Setting (
DIP SWITCH SW1
)
ANC-6000
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
5
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
6
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
7
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ALCN-792MISO
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
Put
in "O
N" posit
ion fo
r
firmware
re
st
or
e
to def
aul
ts durin
g
power
up.
At
all ot
her t
imes put
in "O
FF"
st
at
e.
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
Refer to Network Fire Alarm Manual as to whether addresses 5, 6 and 7 are available
5
ON
OFF
ON
OFF
OFF
OFF
OFF
6
OFF
ON
ON
OFF
OFF
OFF
OFF
7
ON
ON
ON
OFF
OFF
OFF
OFF
RAXN-LCD/G
ADDR
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
33
ON
OFF
OFF
OFF
OFF
ON
Leave in
"OFF"
position as
Factory Set.
34
OFF
ON
OFF
OFF
OFF
ON
35
ON
ON
OFF
OFF
OFF
ON
36
OFF
OFF
ON
OFF
OFF
ON
37
ON
OFF
ON
OFF
OFF
ON
38
OFF
ON
ON
OFF
OFF
ON
39
ON
ON
ON
OFF
OFF
ON
Summary of Contents for FX-MNS-6000