The following table lists all the LEDs located on the UDACT-300A board and states the
function of each LED.
The following table lists the user jumpers available on the UDACT-300A and their functions.
See the
UDACT-300A Installation and Operation Manual LT-888
for more information.
Table 9:
UDACT-300A List of LEDs and their Functions
LEDs
LED Function
Relay Line 1
Located below Line 1 terminal block. When Line 1 relay is energized, this green
LED will illuminate
Relay Line 2
Located below Line 2 terminal block. When Line 2 relay is energized, this green
LED will illuminate.
RS-485
Status LED for communication, will flash when RS-485 communication is active.
Common Trouble
Steady amber for any troubles on the Fire Alarm panel or UDACT-300A.
CPU Fail
Steady amber for any on board CPU trouble.
Telephone Line 1
Telephone status indicator LED; Red when the line is in use, Amber when there is
a line trouble.
Telephone Line 2
Telephone status indicator LED; Red when the line is in use, Amber when there is
a line trouble.
Power ON
Green LED is ON steady when power is supplied to the board.
Table 10:
UDACT-300A List of Jumpers for Operation and Configuration
Jumper Number
Jumper Function
JW1
Normally open. Place jumper here and power down the UDACT-300A by
disconnecting P1 or power down the fire alarm panel (AC and Batteries), then
power back to revert to default passcode. After reset, remove the jumper. Leave
normally open.
JW2
Normally open to BLOCK remote configuration via modem, PC with a UIMA
converter module or using the LCD and keypad at the UDACT-300A. Place jumper
here to ALLOW any type of configuration. Remove jumper once configuration is
complete.
Note:
This module cannot be installed if a city tie module is used.