42
Figure 29 Main Fire Alarm Control board Field Terminal Connections (continued)
Note:
All circuits are power limited (unless marked otherwise) and must use type FPL,
FPLR, or FPLP power limited cable.
NACs are fully supervised and rated for regulated 24 VDC, 1.
7
A max. They must
be wired as shown in the Wiring Tables and Information
on page
58.
BELL, HORN, OR
STROBE
Legend:
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
SUPERVISED NAC # 1
INDICATION
NAC 0
NAC 1
NAC 2
NAC 3
CIRCUIT 1
(POWER-LIMITED)
(POWER-LIMITED)
(POWER-LIMITED)
(POWER-LIMITED)
(POWER-LIMITED)
CLASS A
WIRING
CLASS A
WIRING
INDICATION
CIRCUIT 2
CLASS B
WIRING
CLASS B
WIRING
SUPERVISED NAC # 0
ANALOG
POWER-LIMITED, REGULATED
POWER-LIMITE
D
LOOP 2
CONNECTIONS
(LOOP 0 AND
LOOP1 ARE
INTERNAL
ADDRESSES
FOR FIRST 8
CARDS AND
SECOND 8
CARDS
RESPECTIVELY
+
4-WIRE
POWER
SUPPLY
-
+
AUX. POWER
-
TRB
RTI
INTERFACE
E+
TS2
I+
_
TRL
ANALOG LOOP FIELD WIRING
(CLASS A OR B)
SEE ANALOG LOOP WIRING SECTION
POWER-LIMITED, 22V DC, 400 mA MAX
Maximum Loop Resistance 40 ohms
22V DC, 400 mA MAX
5 mV Ripple
CONNECTION TO MIRCOM RTI
REMOTE TROUBLE INDICATOR
(SEE RTI INSTALLATION
INSTRUCTION) BLK TO TRB+ BLU
TO TRL-RED & WHT TO AUX.
POWER COM+
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
2
3
4
1
6
5
+
-
+
-
TO
INITIATING
CIRCUIT
+
-
+
-
POWER
+
-
DETECTION
4-WIRE
DETECTION
DEVICE
AUXILIARY POWER
FOR REMOTE ANNUNCIATORS
24 VDC SPECIAL APPLICATION
1.7 AMPS MAXIMUM
RTI
BLK
BLU
RED & WHT
2
P
O
O
L
B
A
+
-
+
-
+
-
-
+
+
+
-
-
SUPERVISED NAC # 3
INDICATION
CIRCUIT 1
INDICATION
CIRCUIT 2
SUPERVISED NAC # 2
+
-
-
+
+
+
-
-
NAC External Power
Connection
NOT USED
NOT USED
TS2 Terminal Block is located on the
bottom right corner of the main fire
alarm board.
Connect WC-100015 harness
to P10+ and QPS-6650 DCA +
Class B
i