background image

www.mircom.com 

LT-2070

 Rev. 2 July 2018

MS-400AP(U) Series

Fire Alarm Manual Station

1

Mircom’s MS-400AP(U) Series Fire Alarm Manual Stations 
provide manual fire alarm activation. These high quality, die-cast 
metal stations are available as one stage or two stage stations. 
On the two stage model, use a key to activate the stage two 
alarm. Each station has a permanently attached AP addressable 
module, which has a pair of dials for setting the address.

Specifications & Dimensions

Compatible with Mircom Fire Alarm Control Panels

Electrical Rating:

Dimensions:

MS-401AP(U)

 

4.55” H x 3.3” W x 2” D

MS-402AP, MS-407AP(U): 4.55

” H x 3.3” W x 2.1” D

Installing the manual station

This guide covers these models:

MS-401AP(U) Intelligent Single Stage Manual Station AP
MS-402AP Intelligent Two Stage Manual Station AP
MS-407AP(U) Intelligent Single Stage Manual Station AP with 
additional N.C. switch
The suffix 

U

 indicates a USA version.

Contents of kit

MS-401AP(U), MS-407AP(U): 2 mounting screws, 1 glass 
rod (sold separately)

MS-402AP: 2 mounting screws, 2 stage two keys, 1 glass rod 
(sold separately)

A. Wiring

Note:

The maximum wire size is 12 AWG.

1.

Connect the black (-) wire from the previous station to 
the terminal that is connected to the black (-) wire from 
the addressable module.

2.

Connect the black (-) wire leading the next station to the 
other side of the terminal that is connected to the black 
(-) wire from the addressable module.

Note:

The wires must be on opposite sides of the set screw. 
Refer to Figure 2 for the location of the wires.

3.

Tighten the (-) terminal.

4.

Connect the red (+) wire from the previous station to the 
terminal that is connected to the red (+) wire from the 
addressable module.

5.

Connect the red (+) wire leading to the next station to the 
other side of the terminal that is connected to the red (+) 
wire from the addressable module.

Note:

The wires must be on opposite sides of the set screw. 
Refer to Figure 2 for the location of the wires.

6.

Tighten the (+) terminal.

MS-402AP

MS-401AP(U), MS-407AP(U)

Nominal Operating Voltage: 
15-32 VDC

Nominal Operating Voltage: 
15-32 VDC

Maximum alarm current @ 24V: 
5.4 mA

Maximum alarm current @ 24V: 
600 µA

Average operating current @ 
24V: 600 µA

Average operating current @ 
24V: 400 µA

Notes

• Wire as shown so that supervision of connections is 

maintained.

• Maximum wire size: 12 AWG
• All manual fire alarm stations shall be installed as per 

the specific requirements outlined in the UL/ULC codes, 
as well as all other applicable national or local codes.
Final acceptance is subject to the local authority having 
jurisdiction.

-

  BLACK

}

+

 RED

}

-

-

+

+

ADDRESSABLE
MODULE

TO NEXT STATION OR 
END OF LINE DEVICE

FROM 

PREVIOUS 

STATION

AUXILIARY FUNCTION

N.C. SWITCH

(MS-407AP(U) ONLY)

}

Figure 1: Wiring Diagram

TO ADDRESSABLE
MODULE

WRONG: BOTH 
WIRES ON THE 
SAME SIDE AS 
THE SET SCREW

TO ADDRESSABLE
MODULE

CORRECT: BOTH 
WIRES ON
OPPOSITE SIDES 
OF THE SET SCREW

X

Figure 2: Close-up of terminals showing correct wiring