background image

English – 

15

English

Additional pairs of photocells can be installed at any time on a system for sliding gates.
Up to a maximum of 6 pairs of photocells with safety functions can be added (as shown in the example 

A-B-C-D-E-F

in 

fig. 31) and 1 pair 

with

a control function (as shown in the example

G

in 

fig. 31

) which performs an 

Opening

manoeuvre only.

For the correct location of these pairs of photocells, refer to 

fig. 31

.

In order for the control unit to recognise each pair of photocells and the specifically assigned function, the devices must be assigned with
addresses by the insertion of one or two electric jumpers (

Table 2

) or no jumper at all (

Table 2

). In this way when the control unit receives the

input from the photocells it will activate the motor for the corresponding manoeuvre.

The address assignment procedure is performed both on the TX and RX photocell as follows:

For photocells “

A-B-C-D-E-F

Take care to observe the following warnings:
• 

the electric jumpers must be positioned on the two elements making up the pair of photocells (TX and RX) in the same position;

• the same configuration used on one pair of photocells must NOT be used on other photocells.

To program these pairs of photocells (if fitted on the system) proceed as follows:

01.

Open the cover of the photocell.

02.

In 

fig. 31

locate the position in which the specific photocells are installed. 

03.

In 

Table 2

select the required configuration and insert electric jumpers in the two photocells.

For photocells “

G

Take care to observe the following warnings:
• These photocells have a different function from the other (controlling the automation), and therefore must be positioned at a specific distance
to avoid possible interference.
• These photocells remain powered also when the automation is on standby and in the event of a power failure, if the buffer battery is fitted, this
will reduce the standard lifetime (see STEP

6.5

).

To program these pairs of photocells (if fitted on the system) no electric jumper must be inserted (

see Table 2

).

SELECTING THE PHOTOCELL PAIR OPERATING MODE

TABLE 2

Pair of photocells

Electric jumpers

A

Photocells h = 50 cm

(these are activated when
the gate is in the Closing phase)

B

Photocells h = 100 cm

(these are activated when
the gate is in the Closing phase)

C

Photocells h = 50 cm

(these are activated when
the gate is in the Opening
or Closing phase)

D

Photocells h = 100 cm

(these are activated when

the gate is in the Opening
or Closing phase)

Pair of photocells

Electric jumpers

E

Photocells on right

(these are activated when
the gate is in the Opening phase)

F

Photocells on left

(these are activated when
the gate is in the Opening phase)

G

Gate 

opening

only command

31

Summary of Contents for Moovo LN4 Series

Page 1: ......

Page 2: ...unit 12 6 2 Installing and connecting flashing light mod MF 12 6 3 Installing and connecting photocells mod MP 14 Selecting the photocell pair operating mode 15 6 4 Installing and connecting keypad m...

Page 3: ...If this is the first time you are setting up an automation for sliding gates we recommend that you read this entire manual with care This is prefer able before any work without any hurry to start prac...

Page 4: ...trol unit can memorise up to 150 keys of MT4 transmitters up to 4 MK control keypads or alternatively up to 4 pairs of MP photocells set for the opening command only Connections of the various devices...

Page 5: ...f accidental impact Ensure that the selected surfaces for fixing the photocells are flat and enable correct alignment between photocells 3 2 CHECKING PRODUCT APPLICATION LIMITS To ascertain suitabilit...

Page 6: ...nals on the control unit mixed this configuration is a combination of the two configurations described above To select the most suitable connection configuration for the connection of all system devic...

Page 7: ...edded in concrete and other preparation work for the installation can be com pleted to finalise the site ready for subsequent installation operations In particular for digging the pit for anchoring th...

Page 8: ...fectly level use a spirit level 04 When the concrete is solid after a few days loosen and remove the upper nuts of the plate which are no longer required 05 Remove the gearmotor cover using a screwdri...

Page 9: ...t so move the bracket to this position and if necessary use a hacksaw to cut off the excess section of the rack leaving a free section of approx 5 cm IMPORTANT the rack must not protrude from the gate...

Page 10: ...NECTIONS OF SYSTEM DEVICES Install and connect the system devices with reference to the STEPS below and the example in fig 17 CAUTION Incorrect connections can cause faults or hazards therefore ensure...

Page 11: ...icates execution of each manoeuvre It is also con nected to the diagnostics system of the control unit and in the event of malfunctions signals the type of problem by means of a pre set sequence of fl...

Page 12: ...the cap of the flashing unit in its seat until the tabs click in place 21 20 22 08 Fig 23 Refit the transparent cover in its seat and turn clockwise taking care that the serrated section engages with...

Page 13: ...p by pushing down one side as shown in the figure 02 Fig 26 Using a screwdriver open and detach the base of the photocell 03 Fig 27 a Drill a hole on the pre cut section on the base for routing the co...

Page 14: ...oceed as follows 01 Open the cover of the photocell 02 In fig 31 locate the position in which the specific photocells are installed 03 In Table 2 select the required configuration and insert electric...

Page 15: ...ypad cover by pushing down one side as shown in the figure 02 Fig 33 Using a screwdriver open and detach the base of the keypad 03 Fig 34 a Drill a hole on the pre cut section on the base for routing...

Page 16: ...id the risk of leaks of harmful sub stances Battery disposal CAUTION Even if discharged the batteries can contain pollutant sub stances and therefore must NEVER be disposed of in common waste col lect...

Page 17: ...nnections refer also to the paragraph What to do if 41 L2 green led L1 red led Key P1 STEP 7 WARNINGS The PVC power supply cable supplied serves exclusively for automation operation and programming te...

Page 18: ...ing light 1 flash and the keypad 1 beep if fitted on the system 05 on the keypads Activate the keypads if fitted on the system by pressing any key on each one as required Successful learning is confir...

Page 19: ...ey for example Command 2 03 Press P1 on the Control unit the same number of times as the selected command number in the example 2 i e twice and check that the green led emits the same number of quick...

Page 20: ...press key T3 Leaf deceleration points press key T4 04 Lastly refer to Table 3 select the required value in correspondence with the selected function and on the transmitter press the key asso ciated w...

Page 21: ...s first then the red led illuminates after 5 seconds and then both to indicate that the Control unit has entered memory deletion mode Then release the key 02 With reference to Table 4 select the data...

Page 22: ...version of movement The automation does not respond to commands After a series of manoeuvres sent consecutively the automation is blocked The automation does not respond to commands The automation doe...

Page 23: ...rictly observed In the case of this product the cable supplied may need to be replaced with a protected electric line suited to the installation In this case use a power cable with the dimensions 3 x...

Page 24: ...ll devices used and the declaration of conformity compiled by the installer see section TECHNICAL DOCUMENTATION 2 Affix a dataplate on the door specifying at least the following data type of automatio...

Page 25: ......

Page 26: ...ered and sends the output signals Absorbed power 120mW in funzionamento 45mW in stand by Ambient operating temperature 20 50 C Use in acid saline or potentially No explosive atmospheres Assembly Verti...

Page 27: ......

Reviews: