TROUBLESHOOTING PROCEDURES FOR MH006 AND MH007
Issue
Cause
What to do
After installation,
the unit doesn’t
work.
1. The power source is not turned ON.
1. Make sure the circuit breaker and the unit’s
power is ON.
2. The power line and the cable locking connector
is not connecting properly.
2. Check the power connection with the unit is
connected properly.
3. The switch board and control board wirings are
disconnected.
3. Make sure the wirings between the switch
board and control board are connected
properly.
4. The switch board or control board is defective.
4. Change the switch board or control board.
Light works, but
blower is not
turning.
1. The blower wire is not connected.
1. Make sure the blower wire is plugged into the
molex connector.
2. Blower molex plug pin is not making contact.
2. Disconnect the blower molex plug, check pins
inside plug to see if pin is pushed inside the
plug too far. Reseat pin if needed.
3. The blower is defective, possibly seized.
3. Change the blower.
4. The thermally protected system detects if the
blower is too hot to operate and shuts the blower
down.
4. The blower will function properly after the
thermally protected system cool down.
5. Damaged capacitor.
5. Change the capacitor.
6. The switch board or control board is defective.
6. Change defective part.
The unit is
vibrating.
1. The blower is not secured in place.
1. Tighten the blower in place.
2. Damaged blower wheel.
2. Replace the blower.
3. The hood is not secured in place.
3. Check the installation of the hood.
The blower is
working, but the
lights are not.
1. The light bulb plug is disconnected.
1. Connect the light bulb plug.
2. Defective halogen bulb.
2. Change the halogen bulb.
3. The light bulb is loose.
3. Tighten the light bulb.
The hood is
not venting out
properly.
1. The hood might be hanging to high from the
cook top.
1. Adjust the distance between the cook top and
the bottom of the hood within 26” and 34”
range.
2. The wind from the opened windows or opened
doors in the surrounding area are affecting the
ventilation of the hood.
2. Close all the windows and doors to eliminate
WKHRXWVLGHZLQGÀRZ
3. Blockage in the duct opening or ductwork.
3. Remove all the blocking from the duct work or
duct opening.
4. The direction of duct opening is against the wind.
4. Adjust the duct opening direction.
5. Using the wrong size of ducting.
5. Change the ducting to at least 6” or higher.
Metal Filter is
vibrating.
0HWDO¿OWHULVORRVH
&KDQJHWKHPHWDO¿OWHU
Summary of Contents for MH00630AS