MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-6
The UPS must be installed and operated in a controlled environment.
An improper storage and installation environment will deteriorate insulation,
shorten component life, cause corrosion and equipment malfunctions, and can
void your warranty. The standard installation and operational environment is
as follows:
Table 1
UPS Installation and Operational Environment
Category
Acceptance Criteria
Installation
Location
Indoors, completely weather-protected location
Altitude
0
– 2255 m
(
1524
– 2255 m
requires derating, contact MEPPI)
Ambient
Temperature
32°F (0°C) to 104°F (40°C)
Ideal operating temperature for batteries: 68°F (20°C) to 77°F (25°C)
Relative Humidity
5% to 95% with no condensation
Solid
Contaminants
(See Note 1)
Parameter
Maximum value
Sand
0
Dust/ Particulate matter
(suspension)
<0.01 mg/m
3
Dust/ Particulate matter
(sedimentation)
<0.4 mg/(m
2
·h)
Chemical
Contaminants
(Gases and
Vapors)
Parameter
Mean value (See Note
2)
Maximum Value (See
Note 3)
Sea salts
0
0
Sulfur dioxide (SO
2
)
<0.01 PPM
<0.03 PPM
Hydrogen sulfide (H
2
S)
<0.003 PPM
<0.01 PPM
Wet Chlorine (Cl
2
)
relative humidity >50%
<0.0005 PPM
<0.001 PPM
Dry Chlorine (Cl
2
)
relative humidity <50%
<0.002 PPM
<0.01 PPM
Hydrogen chloride (HCl)
<0.0066 PPM
<0.0066 PPM
Hydrogen fluoride (HF)
<0.001 PPM
<0.005 PPM
Ammonia (NH
3
)
<1 PPM
<5 PPM
Ozone (O
3
) or other
oxidants
<0.002 PPM
<0.005 PPM
Nitrogen oxides (NO
x
)
<0.05 PPM
<0.1 PPM
Aerosols
Oils
<5 PPB dry air
Flora and Fauna
None (no presence or risk of growing mold or fungus; negligible risk of damage
WARNING 3
4
WARNING