MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-4
3.4 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 9 for list of UPS weights.
Table 9
List of UPS Weights
UPS Capacity (kVA)
10
20
30
40
50
60
70
80
Weight (lb.)
499
543
587
631
675
719
763
807
B) Minimum clearance required for ventilation:
Right side
1.0" (25 mm) (not required when sidecars are used)
Left side
1.0" (25 mm) (not required when sidecars are used)
Back side
8.0" (203 mm)
Top side
16.0" (406 mm)
C) Space requirement for routine maintenance:
Allow for the following space at the time of installation.
Front
31.5" (800 mm)
Sides
1.0" (25 mm)
Rear
8.0" (203 mm)
Top side
16.0" (406 mm)
Figure 33
Clearance for Ventilation and Maintenance
!
NOTE
16" (406mm)
For Air exhaust
and Maintenance
31.5" (800mm)
For Maintenance
8" (203mm)
For Air exhaust
Side View
Summary of Contents for 1100B Series
Page 2: ...Preface ...
Page 64: ......