52
[Wiring example when using a duct (problematic example and
modification example)]
(f) CC-Link IE Field Network module
The precautions for using CC-Link IE Field Network cables are
described below.
• For CC-Link IE Field Network module, use CC-Link IE Field
Network cables (SC-E5EW-S M, manufactured by
Mitsubishi Electric System & Service Co., Ltd.).
• A CC-Link IE Field Network cable is a shielded cable.
Remove a part of the shield as shown below and ground the
largest possible exposed section to the ground.
To ground the cables for external wiring, refer to Section 4.1
(3) (d)
Relay
Relay
Relay
Programmable
controller
Relay
Relay
Relay
Modified
Wiring duct
Wiring duct
Control
panel
Control
panel
Drive
unit
Drive
unit
Noise source
(Power system,
etc.)
The drive units are placed
near the noise source. The
connection cable between
the programmable controller
and drive units is too long.
Noise source
(Power system,
etc.)
Drive
unit
Drive
unit
The programmable
controller and drive
units are placed closely.
The connection cable
between them is located
separately from the power
line, and is as short as
possible. (In this example,
the cables are connected
without using the duct.)
Programmable
controller
CC-Link IE Field Network cable
Shield