background image

8

5. Installing the refrigerant piping

(3)Use the following procedure for connecting the gas-side piping. (Fig. 5-2)

1.Remove the flange and packing attached to the valve body. These were mounted

at the time of shipping from the factory to prevent refrigerant leakage.
* Never attempt to reuse this packing as refrigerant leakage will occur.

2.Braze the flange joint 

2

 provided to the outdoor unit using locally procured

brazing materials.
* Always perform this brazing before mounting the stop valve.

3.Always attach the new packing 

3

, provided, for the connecting pipe with the

flange to the valve body before connecting the piping to the stop valve.
* The tightening torque for M10 bolts for the flange joint : 25.2 N·m ±15%.

(4)After connecting the installing bolts for the refrigerant piping, check for gas leak-

age in the locally installed piping and indoor units.

Table 3 (Fig. 5-3)

Copper pipe O.D.

A (mm)

(mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4")

1.0 - 1.5

0 - 0.5

ø9.52 (3/8")

1.0 - 1.5

0 - 0.5

ø12.7 (1/2")

1.0 - 1.5

0 - 0.5

ø15.88 (5/8")

1.0 - 1.5

0 - 0.5

ø19.05 (3/4")

1.0 - 1.5

0 - 0.5

5.3. Refrigerant piping (Fig. 5-4)

Remove the service panel 

A

 (eight screw).

(1) Perform refrigerant piping connections for the indoor/outdoor unit when the out-

door unit’s stop valve is completely closed.

(2) Vacuum-purge air from the indoor unit and the connection piping.
(3) After connecting the refrigerant pipes, check the connected pipes and the indoor

unit for gas leaks. (Refer to 5.4 Refrigerant pipe airtight testing method)

(4) Vacuumize the refrigerant lines through the service port of the liquid stop valve

and then open the stop valves completely (for both the liquid and gas stop valves).
This will completely connect the refrigerant lines of the indoor and outdoor units.

• If the stop valves are left closed and the unit is operated, the compressor and

control valves will be damaged.

• Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque.

Valve size

Tightening torque N·m (kgf·cm)

Valve cap

Service port cap

3/8 ø9.52

22-28 (220-280)

12-16

1/2 ø12.7

25-31 (250-310)

(120-160)

1 ø25.4

36-44 (360-440)

11.5-13.9 (115-139)

Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.

(5) Use sealant to seal the ends of the thermal insulation around the pipe connection

sections to prevent water from entering the thermal insulation.

5.4. Refrigerant pipe airtight testing method (Fig. 5-5)

(1) Connect the testing tools.

• Make sure the stop valves 

A

 

B

 are closed and do not open them.

• Add pressure to the refrigerant lines through the service port 

C

 of the liquid

stop valve 

D

.

(2) Do not add pressure to the specified pressure all at once; add pressure little by little.

1

 Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the

pressure does not decrease.

2

 Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait five minutes, and make sure the

pressure does not decrease.

3

 Pressurize to 3.6 MPa (36 kgf/cm

2

G) and measure the surrounding tempera-

ture and refrigerant pressure.

(3) If the specified pressure holds for about one day and does not decrease, the pipes

have passed the test and there are no leaks.

• If the surrounding temperature changes by 1 °C, the pressure will change by

about 0.03 MPa (0.3 kgf/cm

2

G). Make the necessary corrections.

(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the

source of the gas leak.

A

 Die

B

 Copper pipe

A

A

B

Fig. 5-3

A

Service panel

B

Right-side piping (Knock-out)

C

Lower piping (Knock-out)

D

Front piping (Knock-out)

A

Stop valve <Liquid side>

B

Stop valve <Gas side>

C

Service port

D

Open/Close section

E

Local pipe

F

Sealed, same way for gas side

G

Pipe cover

H

Packing (Provided part)

I

Connecting pipe (Provided part)

J

Use non-oxidizing brazing material on flange joint.

K

Locally procured pipe connection

M10
Bolt

Fig. 5-4

Fig. 5-5

1

Main unit of valve

2

Flange connection

3

Packing

4

Always change to the new
packing provided.

5

Local piping

3

4

1

2

5

A

B

C

D

A

C

D

E

F

G

B

C

D

H

I

E
J

K

Fig. 5-2

Summary of Contents for 250 YHA-A

Page 1: ...English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP200 250 YHA A FOR INSTALLER ...

Page 2: ... it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Cons...

Page 3: ... in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Fl...

Page 4: ...e overall height of the unit add the dimen sion shown as h in the drawing on the left to L1 and L2 on Table 2 Table 2 mm L1 L2 450 100 2 4 2 When installing multiple outdoor units Fig 2 8 When installing multiple units make sure to take into consideration factors such as providing enough space for people to pass through ample space between blocks of units and sufficient space for air flow as shown...

Page 5: ...openings at the base of the unit Note 1 Always use care when transporting a unit by forklift on rainy days as slip page can occur 2 Never use dangerous sudden movements such as accelerating or applying the brakes suddenly or turning the steering wheel quickly when transporting the unit by forklift 3 2 Transporting by pallet truck Fig 3 2 When using a pallet truck to transport the unit insert the f...

Page 6: ... stalled has sufficient strength If the surface is not strong enough the unit could fall over and cause damage or injury Make sure that the unit is installed so that it will be able to withstand earth quakes and strong winds Damage or injury could occur if the unit tips over due to an earthquake or strong wind Be sure to install the unit in a sturdy level surface to prevent rattling noises during ...

Page 7: ...ne foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut A Use two wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are com pleted Apply refrigerating machine oil over the entire flare seat surface C Do not apply...

Page 8: ...air from the refrigerant lines After the valve work is completed tighten the valve caps to the correct torque Valve size Tightening torque N m kgf cm Valve cap Service port cap 3 8 ø9 52 22 28 220 280 12 16 1 2 ø12 7 25 31 250 310 120 160 1 ø25 4 36 44 360 440 11 5 13 9 115 139 Failure to replace and tighten the caps may result in refrigerant leakage In addition do not damage the insides of the va...

Page 9: ... less 41 50 m and less 51 60 m and less 61 70 m and less 71 120 m and less 0 9 kg 1 8 kg 2 7 kg 3 6 kg 1 2 kg 2 4 kg 3 6 kg 4 8 kg Outdoor unit RP200 RP250 At time of shipping kg 10 5 10 5 No additional charge necessary Calculate the amount of additional refrigerant charge using formula provided below Main piping Liquid line size ø9 52 overall length 0 09 Gasline ø28 58 m 0 09 kg m Branch piping L...

Page 10: ...ner from the pipes The existing piping can be reused After flaring the pipes again connect the new air conditioner The existing pipes cannot be reused Use new pipes 5 Installing the refrigerant piping 5 8 For twin triple quadruple combination Fig 5 8 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In additi...

Page 11: ...ting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied The earth wire should also be thicker than the power supply cord so that it can stand any surge of electricity when trouble occurs 7 2 Field electrical wiring If the wiring connecting t...

Page 12: ...ended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malfunction Perform the following procedures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulation resistance is below 1 MΩ the compressor is faulty or the resist ance dropped due the accumulation of refrigerant in...

Page 13: ...W4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from the check valve due to the small differ...

Page 14: ...ltaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 ON OFF 3 4 5 6 E SW 1 3 6 ON OFF 3 4 5 6 F SW 1 3 6 ON OFF 3 4 5 6 G SW 1 3 6 Operation according to switch setting ON OFF Start Normal Clear Normal Settings for outdoor unit ad dresses 0 to 15 SW1 Function table SW1 Function 1 Compulsory de frosting 2 Error history clear 3 4 5 6 ON 1 2 3 4 5 6 OFF TB4 TB5 TB1 TB4 TB...

Page 15: ......

Page 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U638H03 ...

Reviews: