Contents

1. Safety precautions

1.1. Before installation and electric work

s

Before installing the unit, make sure you read all the “Safety
precautions”.

s

The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the
unit.

Symbols put on the unit

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Beware of electric shock. (This symbol is displayed on the main unit label.)

<Color: yellow>

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

Ask the dealer or an authorized technician to install the air conditioner.

- Improper installation by the user may result in water leakage, electric shock,

or fire.

Install the unit at a place that can withstand its weight.

- Inadequate strength may cause the unit to fall down, resulting in injuries.

Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.

- Inadequate connection and fastening may generate heat and cause a fire.

Prepare for strong winds and earthquakes and install the unit at the speci-
fied place.

- Improper installation may cause the unit to topple and result in injury.

Always use an filter and other accessories specified by Mitsubishi Elec-
tric.

- Ask an authorized technician to install the accessories. Improper installation

by the user may result in water leakage, electric shock, or fire.

Never repair the unit. If the air conditioner must be repaired, consult the
dealer.

- If the unit is repaired improperly, water leakage, electric shock, or fire may

result.

Do not touch the heat exchanger fins.

- Improper handling may result in injury.

If refrigerant gas leaks during installation work, ventilate the room.

- If the refrigerant gas comes into contact with a flame, poisonous gases will

be released.

Install the air conditioner according to this Installation Manual.

- If the unit is installed improperly, water leakage, electric shock, or fire may

result.

Have all electric work done by a licensed electrician according to “Elec-
tric Facility Engineering Standard” and “Interior Wire Regulations” and
the instructions given in this manual and always use a special circuit.

- If the power source capacity is inadequate or electric work is performed im-

properly, electric shock and fire may result.

Securely install the outdoor unit terminal cover (panel).

- If the terminal cover (panel) is not installed properly, dust or water may enter

the outdoor unit and fire or electric shock may result.

When installing and moving the air conditioner to another site, do not
charge it with a refrigerant different from the refrigerant (R407C) speci-
fied on the unit.

- If a different refrigerant or air is mixed with the original refrigerant, the refrig-

erant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant leaks.

- Consult the dealer regarding the appropriate measures to prevent the safety

limit from being exceeded. If the refrigerant leak and cause the safety limit to
be exceeded, hazards due to lack of oxygen in the room could result.

When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.

- If the air conditioner is installed improperly, water leakage, electric shock, or

fire may result.

After completing installation work, make sure that refrigerant gas is not
leaking.

- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or

other heat source, it may generate noxious gases.

Do not reconstruct or change the settings of the protection devices.

- If the pressure switch, thermal switch, or other protection device is shorted

and operated forcibly, or parts other than those specified by Mitsubishi Elec-
tric are used, fire or explosion may result.

To dispose of this product, consult your dealer.

The installer and system specialist shall secure safety against leakage
according to local regulation or standards.

- Following standards may be applicable if local regulation are not available.

Pay a special attention to the place, such as a basement, etc. where re-
frigeration gas can stay, since refrigeration is heavier than the air.

The appliance is not intended for use by young children or infirm per-
sons without supervision.

Young children should be supervised to ensure that they do not play
with the appliance.

1.2. Precautions for devices that use R407C

refrigerant

 Caution:

Do not use the existing refrigerant piping.

- The old refrigerant and refrigerator oil in the existing piping contains a large

amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.

Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contami-
nant.

- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant residual oil to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor trouble may result.

1. Safety precautions ...................................................................................... 6

1.1. Before installation and electric work .......................................... 6
1.2. Precautions for devices that use R407C refrigerant .................. 6
1.3. Before getting installed .............................................................. 7
1.4. Before getting installed (moved) - electrical work ...................... 7
1.5. Before starting the test run ........................................................ 7

2. Specifications .............................................................................................. 7
3. Confirmation of parts attached ................................................................... 7
4. Space required around unit ........................................................................ 8
5. Lifting method and weight of product .......................................................... 8
6. Installation of unit ........................................................................................ 8

6.1. Installation ................................................................................. 8
6.2. Connecting direction for refrigerant piping ................................ 8

7. Refrigerant piping installation ..................................................................... 8

7.1. Caution ...................................................................................... 8
7.2. Refrigerant piping system .......................................................... 9

8. Additional refrigerant charge ......................................................................... 9

8.1. Additional refrigerant charge ..................................................... 9
8.2. Caution for piping connection/valve operation ........................... 9
8.3. Airtight test, evacuation, and refrigerant charging ................... 10
8.4. Thermal insulation of refrigerant piping ................................... 10

9. Wiring ........................................................................................................ 11

9.1. Caution .................................................................................... 11
9.2. Wiring and fitting capacities .................................................... 11
9.3. Address settings ...................................................................... 12
9.4. Location of wiring connections ................................................ 12
9.5. Examples of refrigerant system address setting ..................... 12
9.6. Capacity control setting method (PEH-P400, 500MYA only) ... 12

10. Test run ...................................................................................................... 12

10.1. Test run .................................................................................... 12
10.2. How to handle problems with the test run ............................... 12
10.3. The following occurrences are not problems or errors ............ 14

Summary of Contents for 250MYA

Page 1: ... uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de aircondit...

Page 2: ...red at the site D Must be open E Wall height H F No restrictions on wall height L1 450 L2 250 PUH P200 250 7 7 2 H L H L L PUH P200 250 L 50 m H 40 m L Ra Rb 70 m L Ra L Rb 50 m Ra Rb 8 m H 40 m h 1 m 1 Single 2 Twin H h L R a R b PUH P200 250 Fig 7 2 1 A mm Å Outdoor unit ı Gas pipe size Ç Liquid pipe size PUH P200 ø25 4 ø12 7 PUH P250 ø28 58 ø12 7 B mm Î Indoor unit ı Gas pipe size Ç Liquid pipe...

Page 3: ...ly open state A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob F Stop valve G Liquid pipe H Gas pipe I Outdoor unit J Service port B Ball valve liquid side Fig 8 4 4 Fig 8 4 3 Fig 8 4 2 C A B D E Fig 8 4 1 B A D C E E E D A B D F G B D Floor fireproofing E I B C Outer wall exposed A B A Inner wall concealed A B D C B Outer wall F H D B G E Roof pipe shaft I A J 1m 1m F Penetra...

Page 4: ...ecting with PEH P400 500 2 With heater B C D PUH P200 250 E E A B C A B C A A B C PUH P200 250 F 0 D A B C PEH P400 500 PUH P200 250 F 1 3 Grouping 16 outdoor units A D E E E E PUH P200 250 F 0 PUH P200 250 F 14 PUH P200 250 F 15 L1 L2 L3 N S1 S2 S3 S1S2 S3 L1 L2 L3 N S1 S2 S3 S1S2 S3 L1 L2 L3 N S1 S2 S3 S1S2 S3 S1S2 S3 B C A B C B C A 5 Grouping 16 outdoor units Connecting with PEH P400 500 A B C...

Page 5: ...N 1 2 3 4 5 6 7 OFF ON 1 2 3 4 5 6 8 OFF ON 1 2 3 4 5 6 9 OFF ON 1 2 3 4 5 6 10 OFF ON 1 2 3 4 5 6 11 OFF ON 1 2 3 4 5 6 12 OFF ON 1 2 3 4 5 6 13 OFF ON 1 2 3 4 5 6 14 OFF ON 1 2 3 4 5 6 15 ø40 ø27 ø27 ø34 ø34 ø38 1 C A B D Fig 9 4 1 9 4 A When installing conduct from bottom panel B When installing conduct from front panel C Mounting plate attached D Knock out hole 9 ...

Page 6: ...t the safety limit from being exceeded If the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that...

Page 7: ...ombine indoor units within the capacity of the outdoor unit Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and flange connections The refrigerator oil will degrade if it is mixed with a large amount of mineral oil Use liquid refrigerant to fill the system If gas refrigerant is used to seal the system the composition of the refriger ant in the cylinder w...

Page 8: ...transmitted to the installation section and noise and vibration may be generated from the floor and walls depending on the installation con ditions Therefore provide ample vibrationproofing cushion pads cushion frame etc Be sure that the corners are firmly seated If the corners are not firmly seated the installation feet may be bent Warning Be sure to install unit in a place strong enough to withs...

Page 9: ...ing with PEH P400 500 Î Indoor unit 2 Twin 3 Triple 4 Four Caution Total bends are 15 units and max bends are 8 units within L R R R R Ra L R R R R Rb L R R R R Rc and L R R R R Rd 25 25 25 25 50 50 33 33 33 25 25 50 20 40 40 Model Additional refrigerant charge 8 Additional refrigerant charge 8 1 Additional refrigerant charge L Main section actual length Ra Rb Rc Rd Join section actual length The ...

Page 10: ...ncrease Turn the flare nut beyond this point by the angle shown in the table above Caution Always remove the connecting pipe from the ball valve and braze it out side the unit Brazing the connecting pipe while it is installed will heat the ball valve and cause trouble or gas leakage The piping etc inside the unit may also be burned Use ester oil ether oil or alkylbenzene small amount as the refrig...

Page 11: ... and connect it correctly Secure it so that the cable applies no external pressure to the terminal connection If the connection is faulty or the cable is not fully secured overheating or fire could result Caution Depending on the location of the unit a current leakage breaker may be required If a current leakage breaker is not installed electric shock could result Do not use breakers or fuses with...

Page 12: ...e operation mode is to be changed first stop it using SW 4 1 then after chang ing the operation mode start the test run again using SW 4 1 If the 2 hour timer is set the test run will stop automatically after 2 hours During the test run the room temperature display on the indoor unit will indi cate the temperature of the indoor unit piping When you operate the test run from OC1 all trial runs are ...

Page 13: ...h on the outdoor unit board the segments light up to indicate the running condition of the unit and the particulars of the check code SW2 setting 123456 000000 011110 010110 110110 011100 111100 Item Operation mode relay output Outdoor unit control condition Indoor unit control condition IC1 IC2 Indoor unit control condition IC3 IC4 Error code history 1 Error code history 2 Display contents tens p...

Page 14: ...he basis of time or piping temperature During defrosting the fan will stop When the supplementary electric heater is ON the fan will run for 1 minute after opera tion stops in order to expel excess hot air during heating only After the switch is turned to ON or until the piping temperature reaches 35 C there will be 5 minutes of light air operation After that there will be 2 minutes of low air ope...

Page 15: ... The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: