MITSUBISHI
ELECTRIC
9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-10
MITSUBISHI ELECTRIC 9700 SERIES UPS
TABLE 1.4
Detail of Specifications
Rated Output kVA
100
150
225
300
375
Rated Output kW
80
120
180
270
338
AC INPUT CHARACTERISTICS
Configuration
3 phase, 3 wire
Voltage
208 V, 480 V, 600 V +10% ~ -15%
Input Power Factor
0.98 Typical
Frequency
60 Hz
±
5%
Reflected Current THD
3% max. at 100% load; 5% max. at 50% load
STATIC BYPASS INPUT
Configuration
3 phase, 3 or 4 wire
Voltage
120/208 V, 277/480 V, 346/ 600 V
±
10%
Frequency
60 Hz (
±
3% Tracking window)
BATTERY
Type
VRLA, Flooded Lead Acid, Nickel Cadmium
Ride Through
Application Specific
Nominal Voltage
360 VDC
Minimum Voltage
290 VDC
Number of Cells
176 ~ 185
AC OUTPUT
Configuration
3 phase, 3 or 4 wire
Voltage
120/208 V, 277/480 V, 346/ 600 V
Voltage Stability
±
1%
Frequency
60 Hz
Frequency Stability
±
0.01% in free running mode
Power Factor
0.8 nominal
0.9 nominal
Power Factor range
0.8 ~ 1.0 lagging (within output kW rating)
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
±
2% maximum at 100% load step
±
1% maximum at loss or return of AC power
±
5% maximum at load transfer to/from static bypass
Transient Recovery
Less than 1 line cycle
Voltage Unbalance
1% maximum at 100% unbalanced load
Phase Displacement
1% maximum at 100% unbalanced load
Inverter Overload
125% for 10 minutes; 150% for 1 sec
System Overload
500% for 2 cycle (with bypass available)
Bypass Overload
125% for 10 minutes
Withstand Rating
65kA* *:with optional fuses
ENVIRONMENTAL
Cooling
Forced Air
Operating Temperature
2
°
F ~ 104
°
F (0
°
C ~ 40
°
C). Recommended 68
°
F ~ 86
°
F
(20
°
C ~ 30
°
C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
3300 Feet (1000 meters); 5000 feet @ 0.99 derating
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell 5Y7/1 (Beige)