9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
MITSUBISHI ELECTRIC 9700 SERIES UPS
Table 3.4
Recommended cable size and torque requirements
Input Side * 1, 2
Output Side * 1, 2
Bypass Side * 1, 2
DC Input Side * 1, 2
kVA
Capacity
Input
Voltage
Output
Voltage
Cable
Size
Torque
in. lbs.
Cable
Size
Torque
in. lbs.
Cable
Size
Torque
in. lbs.
Cable
Size
Torque
in. lbs.
100kVA
208V
208V
300 MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
250 MCM
or larger
347 - 469
in. lbs.
480V 480V 1/0
AWG
or larger
200 - 269
in. lbs.
1/0 AWG
or larger
200 - 269
in. lbs.
1/0 AWG
or larger
200 - 269
in. lbs.
250 MCM
or larger
200 - 269
in. lbs.
600V 600V 3
AWG
or larger
200 - 269
in. lbs.
3 AWG
or larger
200 - 269
in. lbs.
3 AWG
or larger
200 - 269
in. lbs.
250 M]
or larger
200 - 269
in. lbs.
150kVA
208V
208V
600 MCM
or larger
347 - 469
in. lbs.
600 MCM
or larger
347 - 469
in. lbs.
600 MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
480V 480V 3/0
AWG
or larger
347 - 469
in. lbs.
3/0 AWG
or larger
347 - 469
in. lbs.
3/0 AWG
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
600V 600V 1/0
AWG
or larger
347 - 469
in. lbs.
1/0 AWG
or larger
347 - 469
in. lbs.
1/0 AWG
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
225kVA
208V
208V
3x250 MCM
or larger
347 - 469
in. lbs.
3x250 MCM
or larger
347 - 469
in. lbs.
3x250 MCM
or larger
347 - 469
in. lbs.
2x300 MCM
or larger
347 - 469
in. lbs.
480V 480V 300
MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
2x300 MCM
or larger
347 - 469
in. lbs.
600V 600V 4/0
AWG
or larger
347 - 469
in. lbs.
4/0 AWG
or larger
347 - 469
in. lbs.
4/0 AWG
or larger
347 - 469
in. lbs.
2x300 MCM
or larger
347 - 469
in. lbs.
300kVA
208V
480V
3x350 MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
2x600 MCM
or larger
347 - 469
in. lbs.
480V 600
MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
2x600 MCM
or larger
347 - 469
in. lbs.
600V 600V 400
MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
300 MCM
or larger
347 - 469
in. lbs.
2x600 MCM
or larger
347 - 469
in. lbs.
375kVA
208V
480V
3x500 MCM
or larger
347 - 469
in. lbs.
700 MCM
or larger
347 - 469
in. lbs.
700 MCM
or larger
347 - 469
in. lbs.
3x400 MCM
or larger
347 - 469
in. lbs.
480V 2x250
MCM
or larger
347 - 469
in. lbs.
700 MCM
or larger
347 - 469
in. lbs.
700 MCM
or larger
347 - 469
in. lbs.
3x400 MCM
or larger
347 - 469
in. lbs.
600V 600V 600
MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
500 MCM
or larger
347 - 469
in. lbs.
3x400 MCM
or larger
347 - 469
in. lbs.
*1 - Voltage drop across power cables not to exceed 2% of nominal source voltage
*2 - Allowable ampacities based on 90 degree C insulation at an ambient temperature of 30 degree C
Not more than 3 conductors in a raceway without derating.