MITSUBISHI ELECTRIC 9700SERIES UPS
WARNING 2
This UPS does not include a Bypass Input circuit breaker (MCCB). The
Bypass Input contactor (CB3) does not protect against load induced
short circuits. The bypass input circuit breaker (MCCB) is field supplied
and installed. Breaker(MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (VAC) Maximum Bypass
Rating (AAC)
Recommended
Breaker (A)
100 208 278 350
100 480 120 150
100 600
96 100
150 208 416 500
150 480 180 225
150 600 144 150
225 208 625 700
225 480 271 300
225 600 217 225
300 480 361 400
300 600 289 300
375 480 451 500
375 600 361 400