MITSUBISHI ELECTRIC 9900B SERIES UPS
MITSUBISHI
ELECTRIC
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-4
Aerosols
Oils
<5 PPB dry air
Flora and Fauna
None (no presence or risk of growing mold or fungus; negligible risk of damage
from rodents, insects or animals)
Vibration
(Stationary,
sinusoidal)
Parameter
Maximum value
Displacement amplitude (2-9 Hz)
1.5 mm (0.059 in)
Acceleration amplitude (9-200 Hz)
5 m/s
2
(0.51 g)
Vibration
(Non-Stationary,
including shock)
Parameter
Maximum value
Shock response spectrum type L,
peak acceleration å
70 m/s
2
Shock response spectrum type I,
peak acceleration å
0
Shock response spectrum type II,
peak acceleration å
0
Note 1: Solid contaminant and particle examples include, but are not limited to: sand, carbon dust,
metal fillings/dust, conductive particles, and organic and inorganic dust and fibers
Note 2: Mean Value is defined as the average, long-term value
Note 3: Maximum Value is defined as the maximum value occurring over a period of time of not
more than 30 minutes per day
Summary of Contents for 9900B Series
Page 2: ...Preface Revision 4 06 09 2020 U ENM00030 ...