This UPS does not include a Bypass input circuit breaker (MCCB) to protect
the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field
supplied and installed. The recommended Breaker (MCCB) Specifications are
as follows:
Table 1.2
Rating of Bypass Input Circuit Breaker
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (A)
300
480
361
500
500
480
601
800
750
480
902
1200
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and
installed. The overcurrent protection device should be installed in the Battery cabinet
and rated as indicated in Table 1.6.
▲
▲
For other stored energy systems, refer to the attached supplement.
NOTE: The DC input overcurrent protection (Battery disconnect breaker)
hereinafter will be referred as “CB2.”
This UPS functions with lead acid batteries. If a
▲
is seen, review the
supplemental materials for more information about the stored energy
system used.