MITSUBISHI ELECTRIC 9900B SERIES UPS
MITSUBISHI
ELECTRIC
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-22
Table 1.6
Rating of Contactors, Breakers and Fuses
▲
IDENTIFI-
CATION
APPLICATION
OUTPUT CAPACITY OF EQUIPMENT
300kVA
500kVA
750kVA
300kW
500kW
750kW
C
ont
ac
tor
s
CB1
AC input contactor
452A
680A
1005A
CB3
STS contactor
260A
350A
52C
Inverter output contactor
452A
680A
1005A
52S
Bypass contactor
452A
680A
1005A
88RC
Control circuit contactor
20A
Br
eak
er
s
CB2
Battery disconnect breaker
(Recommended)
800A
1400A
2000A
User supply
AC input breaker
(Recommended)
500A
800A
1200A
User supply
Bypass input breaker
(Recommended)
500A
800A
1200A
FPR, FPS, FPT,
FPU, FPV, FPW,
FCR, FCS, FCT,
FCU, FCV, FCW,
FNR, FNS, FNT,
FNU, FNV, FNW,
FBPR, FBPS,
FBPT,
FBNR, FBNS, FBNT
DC fuse
450A / 690V 630A / 690V 800A / 690V
FUA, FUB, FUC
Control power fuse
30A / 600V
FBS1, FBS2, FBS3
Control power fuse
30A / 600V
FOA, FOB, FOC
Control power fuse
30A / 600V
(OPTION)
FSU, FSV, FSW
Bypass input fuse
250A / 690V
315A / 690V
(OPTION)
FEA, FEB, FEC
Parallel control
circuit fuse (optional)
3A / 600V
* Rating would be changed.
▲
For other stored energy systems, refer to the attached supplement.