MITSUBISHI ELECTRIC 9900B SERIES UPS
MITSUBISHI
ELECTRIC
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-15
3.4 OPERATING PROCEDURES
For Parallel Operation system, refer to section “D) MMS Start-up Procedure.”
(Parallel Operation system is herein after MMS [Multi Module System]).
A) Startup Procedure
CAUTION:
Before the UPS startup, the internal Bypass line starts to supply the
unconditioned bypass input power to the critical load if the External
input (or Bypass) Circuit Breaker is closed. Be extremely careful
when closing the External input (or Bypass) Circuit Breaker.
a) Verify that the External Bypass Input Circuit Breaker for each unit is closed (user
supplied).
b) Verify that the Battery Disconnect Circuit Breaker (CB2) is opened or in tripping position.
c) If a dual source is feeding the UPS, close the External AC Input Circuit Breaker manually
(user supplied).
d) The LCD panel boots up automatically, and the screen will show that the Load is powered
by the bypass line.
e) On the LCD panel, select the “OPERATION” tab, and then press the “STARTUP
GUIDANCE” button to proceed with UPS start-up (refer to Figure 2.3).
f) Follow the “STARTUP GUIDANCE” accordingly until the completion of the inverter startup.
NOTE:
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the
inverter start operation can only be performed remotely. If local inverter
start operation is required at the UPS, select "LOCAL ONLY" or
“REMOTE & LOCAL” in the OPERATION MENU.
Summary of Contents for 9900B Series
Page 2: ...Preface Revision 4 06 09 2020 U ENM00030 ...
Page 74: ......