MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-16
Table 1.5
Detail of Specifications
Rated Output kVA
1050
1400
1750
2100
Rated Output kW
1000
1330
1660
2000
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +15% to -20%
Frequency 60
Hz
+/-10%
Reflected Current THD
3% max. at 100% load
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +/-10%
Frequency 60
Hz
+/-5%
BATTERY
Type Lead
Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 3 wire
Voltage 480
V
Voltage Stability
+/-1%
Frequency 60
Hz
Frequency Stability
+/-0.01% in free running mode
Power Factor
0.95
Power Factor Range
0.7 lagging to 0.8 leading
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Transient Recovery
Less than 20ms
Voltage Unbalance
2% maximum at 100% unbalanced load
Phase Displacement
1deg. maximum at 100% load
Inverter Overload
125% for 10 minutes
150% for 60 seconds
System Overload
(with bypass available)
500% for 1 cycle
ENVIRONMENTAL
Cooling Forced
Air
Operating Temperature
32
゚
F to 104
゚
F ( 0
゚
C to 40
゚
C).
Recommended : 68
゚
F to 86
゚
F ( 20
゚
C to 30
゚
C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 to 6500 feet No Derating at 40
゚
C
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell 5Y7/1 (Beige)