MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
2-11
The UPS is equipped with a selectable output contact feature, and above items are the
default settings. Table 2.1 shows the selectable items for output contacts.
Table 2.1
Selectable Items for Output Contacts
No.
Output Item
Default
0 NONE
1 TOTAL
ALARM
OUT8
2 MINOR
FAULT
3 ALARM
4
AC INPUT ABNORMAL
5 BYPASS
ABNORMAL
6 BATTERY
ABNORMAL
7
BATTERY LOW VOL.1
8
BATTERY LOW VOL.2
OUT5
9 BATTERY
DEPLETION
10
OVERLOAD OUT6
11
OVERLOAD PREALARM
12
FAULT GROUP 1
13
FAULT GROUP 2
14
BYPS.SYNCHRONOUS
15
BYPS.ASYNCHRONOUS
16
REMOTE OPE.ENABLE
17
LOAD ON INVERTER
OUT2
18
LOAD ON BYPASS
OUT1
19
LOAD ON AC
20
BATTERY OPERATION
OUT3
21
CONVERTER OPERATION
OUT4
22
INVERTER OPERATION
23
CB1 CLOSE
24
CB2 CLOSE
25
52S CLOSE
26
POWER DEMAND ON
27
EQUALIZING CHARGE
28
ANOTHER BUS SYNC.OK
29
SPARE 29
30
SPARE 30
31
SPARE 31
NOTE: Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC for Detailed
information.