6 - 7 6 - 7
MELSEC-GOT
6 HANDLING
b) Be sure to ground the protective ground terminal of the GOT main unit to the
control panel.
At this time, keep the length of the ground wire grounding the control panel to
within 120mm (4.72inch).
Moreover, be sure to install the ferrite core (TDK brand ZCAT3035-1330)
within 70mm from the protective ground terminal.
(The ferrite core is not used when using the A985GOT RS-422 connection.)
For A985GOT
For Bus connection
For RS-422 connection
A97 /960GOT
INPUT
100-240VAC
(LG)
(FG)
Ferrite core
wi
thi
n
70
m
m
(
2
.76
in
c
h
)
GOT terminal block
Ground to the
control panel
wi
th
in
120m
m
(4.
7
2
in
c
h)
INPUT
100-240VAC
(LG)
(FG)
GOT terminal block
Ground to the
control panel
wi
th
in
1
2
0
mm
(4.
72i
nch)
INPUT
100-240VAC
(LG)
(FG)
Ferrite core
wi
th
in
7
0
mm
(
2
.76 i
n
c
h
)
GOT terminal block
Ground to the
control panel
wi
th
in
120m
m
(
4
.72i
nch)
c) When connecting CC-Link, use the grounding wire of the FG1 terminal on the
CC-Link communication module to connect to the FG terminal of the GOT
power section.
Use a grounding wire of 300 mm or less.
Also, attach the ferrite core (ZCAT3035-1330) within 70 mm of the FG terminal
of A8GT-J61BT13.
DA
1
3
5
7
2
4
6
8
DG
NC
NC
DB
SLD
(FG1)
NC
BD999C127H01
SW
1
2
ON
HOLD
4
OFF
CLEAR
1
GOT FG terminal
CC-Link communication module terminal block
Ferrite core
Wi
th
in
7
0
mm
(2
.76 i
n
c
h
)
Ground wire
(Within 300mm (11.81 inch))