6 - 9 6 - 9
MELSEC-GOT
6 HANDLING
3) For other cables between GOT and GOT
•
Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
•
Do not pass the grounding braided wire on the programmable logic
controller through the core.
Within 150
130
130
GOT side
GOT side
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
Grounding braided
wire(50mm(1.97inch))
Cable shield material
(5.90)
(5.12)
(5.12)
Within 150
(5.90)
b) CPU Direct connection
1) For RS-232C cable (QC30R2)
•
Peel the sheath (with the length shown below) at both ends of the
cable, and expose the shield braided wire for grounding.
130
130
GOT side
PLC side
Within 230
Within 300
40
40
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
(5.12)
(9.06)
(11.81)
(1.57)
(1.57)
(5.12)
2) RS-422 cable (For AC30/100/300R4-25P)
For A985GOT
•
Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
•
Do not pass the braided wire for grounding through the ZCAT2436-
1330 ferrite core.
150
GOT side
PLC side
150
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
Grounding braided
wire(200mm(7.87inch))
Cable shield material
Ferrite Core
(ZCAT2436-1330)
Ferrite Core
(ZCAT2436-1330)
(5.90)
(5.90)