6 - 10 6 - 10
MELSEC-GOT
6 HANDLING
For A97*/960GOT
•
Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
•
Pass the grounding braided wire on the programmable logic controller
side through the core.
130
130
GOT side
PLC side
Within 150
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
Grounding braided
wire(50mm(1.97inch))
Cable shield material
(5.12)
(5.90)
(5.12)
Within 150
(5.90)
c) Computer link connection
1) For RS-232C cable
The RS-232C cable used to connect the GOT, the computer link unit
and PLC CPU with computer link function must be prepared by the user.
The RS-232C cable connection diagram and the connector are as
follows.
Connection diagram
•
If D-sub 9-pin is used for the connector of the computer link unit.
(A1SJ71QC24(-R2), A1SJ71UC24-R2, A1SJ71C24-R2,
A1SCPUC24-R2, A2CCPUC24, QJ71C24(-R2))
Signal
CS(CTS)
RS(RTS)
CD
RD(RXD)
SD(TXD)
DTR(ER)
DSR(DR)
SG
-
Pin No.
8
7
1
2
3
4
6
5
9
Signal
CD
RS(RTS)
CS(CTS)
SD(TXD)
RD(RXD)
DSR(DR)
DTR(ER)
SG
-
Pin No.
1
7
8
3
2
6
4
5
9
GOT side
Computer link module side
Shell
Braided shield
Shell