E-8
3.1 BIF-MD
The unit overview is shown as below.
●(A) LEDs
Name
Indication
Description
Check
POWER
ON
Power is supplied.
OFF
Power is not supplied.
T ERR.
Flashing
Internal transmission fault
Connection of internal transmission cable.
Power supply of Power supply module (P1-P5).
OFF
Normal operating state
RXD
Flashing
Frame reception.
OFF
No reception.
TXD
Flashing
Frame sending.
OFF
No sending.
Modbus ERR.
Flashing
Transmission fault
Setting of Stop bit, Parity, Baud Rate.
Connection of internal transmission cable.
Connection of Modbus cable. Terminator.
Programming (Function code, address, setting data.)
ON
Setting switch fault
Setting of Stop bit, Parity, Baud Rate, Bus address.
OFF
No fault
●(B) RESET Switch
RESET Switch is used to reset the BIF-MD without power off.
After changing the switch while power supply is on, push this switch.
A
B
C
D
E
F
Fig 3.1: Front view
Fig 3.2: Side view
3. Part Names and Settings
G