E-9
ENGLISH
6. Unpacking
1. Make sure that the packing case is free from
any abnormality such as breaking and/or
wetting.
2. Check the rated nameplate to make sure it
is the ordered product. The following content
is described on the rated nameplate.
Rated
nameplate
Not attached
M12
Ue
AED1600-CV
LOW VOLTAGE
A IR CIRCUIT BREAKER
Ir MAX.
POLE
Ui
Ics=100%Icu
with INST. 500VAC
50kA
440VAC
50kA
240VAC
50kA
500VAC
50kA
440VAC
50kA
240VAC
50kA
IEC 60947-2 EN 60947-2 GB/T 14048.2
40
℃
Icw
Cat.B
50kA/1s 36kA/3s
50/60Hz
Uimp 12kV
1000V
P
A
1600
3
Icu
with MCR.
※※※※※※
※※※※※※※※※※※※
1234567891
SERIAL
1
6
2
3
4
11
14
5
7
8
9
10
12
13
AED1600-CV
SWITCH-DISCONNECTOR
Ie
POLE
Ui
Ue
440/500VAC
240VAC
52.5kA
52.5kA
Icm
IEC 60947-3 EN 60947-3 GB/T 14048.3
Cat. AC-23A
Icw
50/60Hz
Uimp 12kV
1000V
P
A
1600
3
※※※※※※
※※※※※※※※※※※※
1234567891
SERIAL
50kA/1s 36kA/3s
1
6
2
15
4
11
14
5
7
13
9
10
(Note)
The fixed type is provided with lifting hooks (HP).
• Low voltage air circuit breaker
• Switch-disconnector
No.
Description
1
Type of circuit breaker
2
Name and size of the circuit breaker
3
Rated current
4
3-pole or 4-pole
5
Rated insulation voltage
6
Rated impulse withstand voltage
7
Rated short-time withstand current
8
Utilization category
9
Rated operating frequency
10
Device type: Circuit breaker or Switch-disconnector
11
Standards
12
Rated ultimate short-circuit breaking capacity
13
Rated operational voltage
14
Serial number
15
Rated operational current